Schneider Electric LC2K16107U7 — Contactors

TeSys K LC2K16107U7 Reversing Contactor, 3P, 16 A AC-3, 230-

MPNLC2K16107U7
Active

Schneider Electric TeSys K reversing contactor, 3P, AC-3 ≤440 V 16 A, 1 NO, 230-240 V AC, IP20, 57 x 90 x 58 mm.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC2K16107U7 — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationMotor control
LC2K16107U7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3 AC-4
LC2K16107U7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC2K16107U7 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC2K16107U7 — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

The coil is 230-240 V AC, 50/60 Hz. IP20 finger-safe terminals (VDE 0106) suit it for enclosed panel mounting — no live parts exposed above the DIN-rail footprint. Ambient range -25 to 50 °C, storage -50 to 80 °C, with no derating up to 2000 m altitude.

Mechanical and environmental specs

Shock-rated: 10 Gn on Y/Z axes (contactor closed), 15 Gn on Y/Z (closed), 6-10 Gn when open. Vibration: 4 Gn closed, 2 Gn open, 5-300 Hz — all per IEC 60068-2-27 and -2-6. Flame retardance meets UL 94 V1 and NF F 16-101/102. Protective treatment TC per IEC 60068 and DIN 50016 for corrosion resistance.

Frequently asked questions

What is the closest alternative to LC2K16107U7 in the TeSys family?

There is no official successor order code listed. A parametric replacement would need to match the 3P reversing contactor form, AC-3 ≤440 V 16 A rating, 1 NO auxiliary, and 230-240 V AC coil. The TeSys K series includes similar reversing contactors; check the spec line yourself for coil voltage and pole count.

MPN
LC2K16107U7