Skip to main content
Schneider Electric LC2K1610C72 — Contactors

Schneider TeSys K LC2K1610C72 Reversing Contactor, 16 A, 36

MPNLC2K1610C72
Active

Schneider Electric TeSys K reversing contactor, LC2K1610C72, 3P, AC-3 ≤440 V 16 A, 1 N/O, 36 VAC coil, preassembled with reversing busbar.

StockContact for availability
Lead time3-5 Days wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LC2K1610C72 — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationMotor control

Ratings & Performance

LC2K1610C72 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-4 AC-3

Contacts & Poles

LC2K1610C72 — Contacts & Poles
ParameterValue
Pole configuration3P

Environmental

LC2K1610C72 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102

Mechanical

LC2K1610C72 — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

The Schneider Electric LC2K1610C72 is a TeSys K reversing contactor — a 3-pole, 3 N/O power pole device with one N/O auxiliary contact, preassembled with a reversing power busbar so it arrives as a single mechanical unit ready for panel mounting. Rated for AC-3 duty at 16 A up to 440 V and AC-4 duty, it is sized for reversing motor control on small induction motors — think conveyors, hoists, or any load that needs forward/reverse switching from a single panel footprint.

The AC-3 rating of 16 A at ≤440 V is the motor-switching current. AC-4 duty is also listed. Rated operational voltage on the power circuit is 690 V AC 50/60 Hz. IP20 protection means touch-safe for panel installation. Operating temperature range is -25 to 50 °C, with storage from -50 to 80 °C. Altitude derating kicks in above 2000 m — no derating needed at typical plant elevations. Mechanical robustness is specified: the contactor withstands 10 Gn shocks (closed) on Y and Z axes, 6 Gn on X, and 4 Gn vibration closed across 5–300 Hz, per IEC 60068-2-27 and -2-6. That is enough for most industrial machinery but not extreme rail or marine shock profiles.

The LC2K1610C72 is a reversing contactor in the TeSys K range. Dimensions are 90 mm wide, 58 mm high, 57 mm deep.

Frequently asked questions

What compliance documentation is available for this part?

The part carries V1 flame retardance per UL 94, and meets NF F 16-101 and NF F 16-102 for fire behaviour. Protective treatment conforms to IEC 60068 and DIN 50016. The manufacturer typically provides RoHS and REACH declarations on request; the evidence does not list specific certificates.

MPN
LC2K1610C72