Specifications

LC2K1610R7 — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationMotor control
LC2K1610R7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3 AC-4
LC2K1610R7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC2K1610R7 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC2K1610R7 — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

Rated 16 A in AC-3 (motor switching) at <=440 V, so it handles a typical 7.5 kW induction motor on a 400 V line. The 440 V AC coil means the control circuit must supply 440 V AC; a 24 V DC or 230 V AC coil version would be a different order code. IP20 finger-safe terminals (per VDE 0106) mean the contactor is intended for installation inside a closed panel, not exposed to washdown or dust.

Installation and compliance notes

The preassembled reversing busbar saves wiring time but locks the pole configuration — no field reconfiguration to 2 NO / 1 NC. Flame retardance meets UL 94 V1 and NF F 16-101/102, so it passes rail and industrial panel fire-safety requirements.

Frequently asked questions

What is the closest alternative to LC2K1610R7?

No official successor order code is provided in the available records. A current TeSys Deca or TeSys island reversing contactor with similar ratings (3P, 16 A AC-3, 440 V coil) would be the functional equivalent, but dimensions and wiring differ — verify fit before ordering.

What compliance documentation is available for this part?

The part carries UL 94 V1 flame retardance certification and conforms to NF F 16-101 and NF F 16-102 for rail applications. IP20 per VDE 0106. No RoHS or REACH statement appears in the available records.

MPN