Specifications
| Parameter | Value |
|---|---|
| Range of product | TeSys K |
| Product or component type | Contactor |
| [Icw] rated short-time withstand current | 90 A 50 °C - 1 s for power circuit 85 A 50 °C - 5 s for power circuit 80 A 50 °C - 10 s for power circuit 60 A 50 °C - 30 s for power circuit 45 A 50 °C - 1 min for power circuit 40 A 50 °C - 3 min for power circuit 20 A 50 °C - >= 15 min for power circuit 80 A - 1 s for signalling circuit 90 A - 500 ms for signalling circuit 110 A - 100 ms for signalling circuit |
| [Ie] rated operational current | 6 A at 10 MOhm for signalling circuit |
| Motor power | 1.5 kW at 220...230 V AC 50/60 Hz 2.2 kW at 380...415 V AC 50/60 Hz 3 kW at 440 V AC 50/60 Hz 3 kW at 480 V AC 50/60 Hz 3 kW at 500...600 V AC 50/60 Hz 3 kW at 660...690 V AC 50/60 Hz |
| Poles description | 3P |
| Pole contact composition | 3 NO |
| Utilisation category | AC-4 AC-3 |
| Depth | 57 mm |
| Width | 45 mm |
| Height | 58 mm |
| Range | TeSys |
| Flame retardance | V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102 |
| Heat dissipation | 3 W |
| Device short name | LC7K |
| Compatibility code | LC7K |
| Device application | Control |