Skip to main content
Schneider Electric LC7K090045FE7

Schneider Electric LC7K090045FE7

MPNLC7K090045FE7
Active

TeSys K contactor, 4P (4 NO), AC,1 <= 440 V 20 A, 115 V AC coil

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LC7K090045FE7 key specifications
ParameterValue
Range of productTeSys K
Control circuit typeAC at 50/60 Hz silent
Product or component typeContactor
Coil voltage115 V AC 50/60 Hz
VoltagePower circuit: 600 V conforming to UL 508 Power circuit: 690 V conforming to IEC 60947-4-1 Power circuit: 600 V conforming to CSA C22.2 No 14
Control circuit voltage limitsOperational: 0.85...1.1 Uc (at Drop-out: 0.1...0.75 Uc (at <50 °C)
[Ue] rated operational voltagePower circuit: 690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Icw] rated short-time withstand current90 A 50 °C - 1 s for power circuit 85 A 50 °C - 5 s for power circuit 80 A 50 °C - 10 s for power circuit 60 A 50 °C - 30 s for power circuit 45 A 50 °C - 1 min for power circuit 40 A 50 °C - 3 min for power circuit 20 A 50 °C - >= 15 min for power circuit
Breaking capacity110 A at 415 V conforming to IEC 60947 110 A at 440 V conforming to IEC 60947 80 A at 500 V conforming to IEC 60947 110 A at 220...230 V conforming to IEC 60947 110 A at 380...400 V conforming to IEC 60947 70 A at 660...690 V conforming to IEC 60947
[Ie] rated operational current20 A (at 16 A (at <70 °C) at 690 V AC AC-1 for power circuit
[Ith] conventional free air thermal current20 A (at 50 °C) for power circuit

All specifications

LC7K090045FE7 additional specifications
ParameterValue
Inrush power in3 VA (at 20 °C)
Hold-in power consumption in3 VA (at 20 °C)
Signalling circuit frequency<= 400 Hz
Poles description4P
Pole contact composition4 NO
Utilisation categoryAC-1
IP degree of protectionIP2X conforming to VDE 0106
Mounting supportPrinted circuit boards
Connections - terminalsSolder pins - busbar cross section: 1.5 x 0.9 mm
Operating altitude2000 m without derating
Depth57 mm
Width45 mm
Height58 mm
Electrical durability0.18 Mcycles 20 A AC-1 at Ue <= 440 V
Mechanical durability10 Mcycles
StandardsEN/IEC 60947-4-1 GB/T 14048.4 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1
RangeTeSys
Operating time30...40 ms coil energisation and NO closing 30 ms coil de-energisation and NO opening
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
Heat dissipation3 W
Average impedance3 mOhm - Ith 20 A 50 Hz for power circuit
Device short nameLC7K
Compatibility codeLC7K
Device applicationControl
Overvoltage categoryIII
Protective treatmentTC conforming to IEC 60068 TC conforming to DIN 50016
Contactor applicationResistive load
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Associated fuse rating25 A gG at 25 A aM for power circuit
Maximum operating rate3600 cyc/h
Safety reliability levelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Irms rated making capacity110 A AC for power circuit conforming to NF C 63-110 110 A AC for power circuit conforming to IEC 60947
Ambient air temperature for storage-50...80 °C
MPN