Skip to main content
Schneider Electric LC7K090087F7

Schneider Electric LC7K090087F7

MPNLC7K090087F7
Active

Contactor, TeSys K, 4P, 2 NO + 2 NC, AC-1, lt or eq to 440V 10A, 110VAC coil

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LC7K090087F7 key specifications
ParameterValue
Range of productTeSys K
Control circuit typeAC 50/60 Hz silent
Product or component typeContactor
Coil voltage110 V AC 50/60 Hz
VoltagePower circuit 600 V UL 508 Power circuit 690 V IEC 60947-4-1 Power circuit 600 V CSA C22.2 No 14
Control circuit voltage limitsOperational: 0.85...1.1 Uc (at Drop-out: 0.1...0.75 Uc (at <122 °F (50 °C))
[Ue] rated operational voltagePower circuit 690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Icw] rated short-time withstand current90 A 122 °F (50 °C) - 1 s for power circuit 85 A 122 °F (50 °C) - 5 s for power circuit 80 A 122 °F (50 °C) - 10 s for power circuit 60 A 122 °F (50 °C) - 30 s for power circuit 45 A 122 °F (50 °C) - 1 min for power circuit 40 A 122 °F (50 °C) - 3 min for power circuit 20 A 122 °F (50 °C) - >= 15 min for power circuit
Breaking capacity110 A at 415 V conforming to IEC 60947 110 A at 440 V conforming to IEC 60947 80 A at 500 V conforming to IEC 60947 110 A at 220...230 V conforming to IEC 60947 110 A at 380...400 V conforming to IEC 60947 70 A at 660...690 V conforming to IEC 60947
[Ie] rated operational current20 A (at 16 A (at <158 °F (70 °C)) at 690 V AC AC-1 for power circuit
[Ith] conventional free air thermal current20 A (at 122 °F (50 °C)) for power circuit

All specifications

LC7K090087F7 additional specifications
ParameterValue
Inrush power in3 VA (at 68 °F (20 °C))
Hold-in power consumption in3 VA (at 68 °F (20 °C))
Signalling circuit frequency<= 400 Hz
Poles description4P
Pole contact composition2 NO + 2 NC
Utilisation categoryAC-1
IP degree of protectionIP2X VDE 0106
Mounting supportRail Plate
Connections - terminalsFaston terminals 2 2.8 mm Faston terminals 1 6.35 mm
Operating altitude6561.68 ft (2000 m) without derating
Depth2.2 in (57 mm)
Width1.8 in (45 mm)
Height2.3 in (58 mm)
Electrical durability0.18 Mcycles 20 A AC-1 <= 440 V
Mechanical durability10 Mcycles
StandardsEN/IEC 60947-4-1 GB/T 14048.4 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1
RangeTeSys
Category18402-WORLD SERVICE PARTS(CONTROL ACCESS)
Operating time30...40 ms coil energisation and NO closing 25...35 ms coil energisation and NC opening 30 ms coil de-energisation and NO opening 40 ms coil de-energisation and NC closing
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
Heat dissipation3 W
Average impedance3 mOhm - Ith 20 A 50 Hz for power circuit
Device short nameLC7K
Compatibility codeLC7K
Device applicationControl
Overvoltage categoryIII
Protective treatmentTC IEC 60068 TC DIN 50016
Contactor applicationResistive load
Mechanical robustnessShocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27 Shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27 Shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27 Shocks contactor opened, on X axis6 Gn for 11 ms IEC 60068-2-27 Shocks contactor opened, on Y axis10 Gn for 11 ms IEC 60068-2-27 Shocks contactor opened, on Z axis10 Gn for 11 ms IEC 60068-2-27 Vibrations contactor closed4 Gn, 5...300 Hz IEC 60068-2-6 Vibrations contactor opened2 Gn, 5...300 Hz IEC 60068-2-6
Associated fuse rating25 A gG at 25 A aM for power circuit
Maximum operating rate3600 cyc/h
Safety reliability levelB10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Irms rated making capacity110 A AC for power circuit conforming to NF C 63-110 110 A AC for power circuit conforming to IEC 60947
Ambient air temperature for storage-58...176 °F (-50...80 °C)
MPN