Skip to main content
Schneider Electric LC7K12105B7 — Contactors

Schneider Electric TeSys K LC7K12105B7 Contactor, 3P, 12 A A

MPNLC7K12105B7
Active

Schneider Electric TeSys K contactor, 3P, AC-3 ≤440 V 12 A, 1 NO auxiliary contact, 24 V AC coil, 4 kW motor at 480 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LC7K12105B7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
LC7K12105B7 — Ratings & Performance
ParameterValue
Utilisation categoryAC-4 AC-1 AC-3
LC7K12105B7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC7K12105B7 — Environmental
ParameterValue
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC7K12105B7 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth57 mm

Product details

The LC7K12105B7 is a TeSys K 3-pole contactor rated for control applications. Its headline motor rating is 4 kW at 480 V AC, 50/60 Hz — that's the figure to match against your motor nameplate for the line voltage you're running. The AC-3 utilisation category means it's designed for starting and stopping squirrel-cage induction motors under load, not just resistive switching. At ≤440 V AC-3, it's rated 12 A, so the 4 kW at 480 V lines up with typical IEC motor sizing. The coil is 24 V AC, which is common for panel control transformers, but confirm your control voltage is AC — a DC coil won't hold in on this one. Rated operational current is 20 A for AC-1 duty. Short-time withstand current is 115 A for 1 second on the power circuit. Heat dissipation is 3 W.

TeSys K contactors are the compact workhorses for motor control in industrial panels — conveyors, pumps, fans, compressors up to about 5.5 kW. The 45 mm width and 58 mm height make them a standard fit for 35 mm DIN rail enclosures. The flame retardance rating V1 per UL 94 means the housing material self-extinguishes, which matters for panel certification to UL 508A or IEC 60947.

Frequently asked questions

What motor power does this contactor handle at 480 V?

It is rated for 4 kW at 480 V AC, 50/60 Hz. Also rated 4 kW at 500–600 V and 660–690 V, and 5.5 kW at 380–415 V and 440 V.

What is the coil voltage?

24 V AC. This is a standard control voltage for industrial panels; verify your control transformer supplies AC, not DC.

What compliance documentation does Schneider provide for this part?

The housing is rated V1 conforming to UL 94, and meets requirements 2 of NF F 16-101 and NF F 16-102 for flame retardance. Standard Schneider declarations for RoHS, REACH, and CE are available through their documentation portal.

MPN