Skip to main content
Schneider Electric LC8K12015F7 — Contactors

Schneider TeSys K LC8K12015F7 Reversing Contactor, 12A AC-3,

MPNLC8K12015F7
Obsolete

Schneider Electric TeSys K reversing contactor, 3P, AC-3 ≤440 V 12 A, 1 NC, 110 V AC coil, IP20, 57 mm depth.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LC8K12015F7 — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationMotor control Resistive load
LC8K12015F7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-1 AC-4 AC-3
LC8K12015F7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC8K12015F7 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC8K12015F7 — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

It also carries AC-1 and AC-4 utilisation categories, so it handles resistive loads and plugging/inching duty as well. The 110 V AC coil is built in; the contactor has 3 NO power poles and one NC auxiliary contact. Ambient temperature range for operation is -25 to 50 °C, with storage from -50 to 80 °C.

If you are qualifying a replacement, look for a TeSys K or TeSys D reversing contactor with the same pole configuration, AC-3 current rating (12 A at 440 V), and 110 V AC coil voltage.

Frequently asked questions

What are the key ratings I need to match for a replacement?

The critical specs are: reversing contactor, 3 NO power poles, AC-3 rated 12 A at ≤440 V, 110 V AC coil, and the physical footprint of 90 mm wide × 58 mm high × 57 mm deep. The utilisation categories are AC-1, AC-3, and AC-4. Any replacement must also have IP20 minimum protection for enclosed panel use.

What compliance documentation is available for this part?

The part carries flame retardance V1 per UL 94 and also meets NF F 16-101 and NF F 16-102 (railway fire-smoke-toxicity). Protective treatment conforms to IEC 60068 and DIN 50016. Mechanical robustness is qualified per IEC 60068-2-27 (shock) and IEC 60068-2-6 (vibration).

MPN