LP1K12103BD key specifications
ParameterValue
Auxiliary contacts typetype instantaneous 1 NO
Product or component typeContactor
Minimum switching voltage17 V for signalling circuit
Control circuit voltage limitsOperational: 0.8...1.15 Uc (at Drop-out: >= 0.10 Uc (at <50 °C)
[Ue] rated operational voltagePower circuit: Signalling circuit: 10 MOhm for signalling circuit
Minimum switching current5 mA for signalling circuit
Inrush power in3 W (at 20 °C)
Hold-in power consumption in3 W at 20 °C
Power pole contact composition3 NO
Poles description3P
Utilisation categoryAC-3 AC-3e AC-1 AC-4
IP degree of protectionIP2X

All specifications

LP1K12103BD additional specifications
ParameterValue
Mounting supportRail Plate
Connections - terminalsSpring terminals 1 cable(s) 0.75...1.5 mm²solid Spring terminals 1 cable(s) 0.75...1.5 mm²flexible without cable end Spring terminals 2 cable(s) 0.75...1.5 mm²flexible without cable end
Operating altitude2000 m without derating
Depth57 mm
Width45 mm
Height58 mm
Electrical durability1.3 Mcycles 12 A AC-3 at Ue 1.3 Mcycles 12 A AC-3e at Ue 0.3 Mcycles 20 A AC-1 at Ue 0.02 Mcycles 72 A AC-4 at Ue <= 440 V
Mechanical durability10 Mcycles
StandardsEN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 UL 60947-5-1 CSA C22.2 No 60947-4-1 CSA C22.2 No 60947-5-1 GB/T 14048.4
RangeTeSys
Operating time30...40 ms coil energisation and NO closing 10 ms coil de-energisation and NO opening
Coil technologyWithout built-in suppressor module
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
Heat dissipation1.3 W
Device short nameLP1K
Contactor applicationMotor control Resistive load
Maximum operating rate3600 cyc/h
Safety reliability levelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Ambient air temperature for storage-50...80 °C
Ambient air temperature for operation-25...50 °C
MPN