Skip to main content
Schneider Electric LP1SK0600CD — Contactors

Schneider TeSys LP1SK0600CD Mini Contactor, 2P NO, 12A AC-1,

MPNLP1SK0600CD
Obsolete

Schneider Electric TeSys SK series, LP1SK0600CD mini contactor, 2-pole (2 NO), AC-1 rated 12 A at 690 V, 36 V DC coil, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LP1SK0600CD — Identification
ParameterValue
Product / component typeMini contactor
Series / rangeTeSys
ApplicationResistive load
LP1SK0600CD — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz
Utilisation categoryAC-1
LP1SK0600CD — Environmental
ParameterValue
IP degree of protectionIP2X conforming to VDE 0106
Operating altitude2000 m without derating
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50015
LP1SK0600CD — Approvals
ParameterValue
StandardsEN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1
LP1SK0600CD — Mechanical
ParameterValue
Width27 mm
Height56 mm
Depth55.5 mm

Product details

The 36 V DC coil draws 2.2 W hold-in power, so verify your control transformer can supply that continuously — it's a standard DC control voltage, common in 24-48 VDC panels. This is a mini contactor, not a full-frame power contactor — the 27 mm width and 56 mm height let it fit tight DIN-rail enclosures where panel space is at a premium. The 55.5 mm depth keeps it clear of gland plates in shallow backboxes.

Mounts on standard DIN rail. Power circuit wiring accepts 0.35 to 6 mm² solid or flexible cable — spring-cage or screw terminals, depending on the connector variant. The 0.8 N.m tightening torque on the connector is light; a Pozidriv No. 1 driver is the tool. Two cables per terminal are allowed for daisy-chaining, but only up to 1.5 mm² flexible with ferrules — keep that in mind when looping through multiple contactors. IP2X finger protection per VDE 0106 means the live parts are guarded against accidental contact, but it's not sealed — no washdown rating. Keep it inside the enclosure.

Certified to EN/IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1 — the contactor standard for motor starters and switching. The associated fuse rating is 16 A gI at ≤ 440 V for the power circuit, so coordinate your branch circuit protection accordingly.

Frequently asked questions

What are the key ratings for this contactor?

Rated operational current (Ie) is 12 A at 690 V AC under AC-1 (resistive load). The coil is 36 V DC, drawing 2.2 W hold-in power. Mechanical durability is 10 million cycles, and the maximum operating rate is 1200 cycles per hour.

What compliance documentation does Schneider provide for this part?

The part carries IEC, UL, and CSA certifications per EN/IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1. The rated insulation voltage is 690 V per those standards.

MPN