Skip to main content
Schneider Electric LP2K06013FD — Contactors

Schneider Electric LP2K06013FD TeSys K reversing contactor,

MPNLP2K06013FD
Active

Schneider Electric TeSys K reversing contactor, 3P, AC-3 <= 440 V 6 A, 1 NC, 110 V DC coil, preassembled with reversing power busbar, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LP2K06013FD — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationMotor control
LP2K06013FD — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3 AC-4
LP2K06013FD — Contacts & Poles
ParameterValue
Pole configuration3P
LP2K06013FD — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Shocks contactor opened, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on X axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LP2K06013FD — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

The LP2K06013FD is a TeSys K reversing contactor from Schneider Electric, rated for 3-pole motor control in AC-3 duty up to 6 A at 440 V, with a 110 V DC coil and one NC auxiliary contact. It ships preassembled with the reversing power busbar — no separate wiring of the mechanical interlock or power crossover needed, which saves panel-build time on a reversing starter. The contactor also carries an AC-4 rating for plugging and inching duty, where the motor is reversed or stopped by counter-torque, which stresses the contacts harder. For a small reversing starter on a conveyor, pump, or fan, this part covers the common 3-phase motor range up to roughly 2.2 kW at 400 V.

IP20 finger-safe terminals (per VDE 0106) mean it can sit in a standard enclosure without additional shrouding on the line side. The preassembled reversing busbar keeps the phase crossover internal, so the only field wiring is the incoming power, the motor leads, and the 110 V DC coil circuit. The 110 V DC coil draws a holding current that depends on the specific coil power — verify the coil inrush and seal VA against your DC supply rating. The single NC auxiliary contact (1 NC) is typically wired into the opposite contactor's coil circuit as an electrical interlock, supplementing the mechanical interlock built into the reversing busbar assembly.

Frequently asked questions

What are the key ratings for this reversing contactor?

3-pole, AC-3 motor-switching duty at 6 A up to 440 V, also rated AC-4 for plugging and inching. Coil is 110 V DC. One NC auxiliary contact. Preassembled with reversing power busbar. IP20 finger-safe terminals.

What is the physical size of the LP2K06013FD?

90 mm wide, 58 mm high, 57 mm deep. Mounts on 35 mm DIN rail.

What compliance documentation is available for this part?

The contactor carries V1 flame retardance per UL 94, IP20 per VDE 0106, and protective treatment per IEC 60068 and DIN 50016. It also meets NF F 16-101 and NF F 16-102 for rail fire-smoke-toxicity. Standard Schneider documentation (datasheet, CE declaration, UL file) is available on request.

MPN
LP2K06013FD