Skip to main content
Schneider Electric LP2K0901KD — Contactors

Schneider Electric LP2K0901KD TeSys K Reversing Contactor, 9

MPNLP2K0901KD
Obsolete

Schneider Electric TeSys K reversing contactor, 3P, AC-3 ≤440 V 9 A, 1 NC, 100 V DC coil, IP20, 57 x 90 x 58 mm.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LP2K0901KD — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationMotor control Resistive load
LP2K0901KD — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3 AC-4 AC-1
LP2K0901KD — Contacts & Poles
ParameterValue
Pole configuration3P
LP2K0901KD — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Shocks contactor opened, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on X axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LP2K0901KD — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

Its headline rating: AC-3 duty at ≤440 V, 9 A, with a 100 V DC coil. The 9 A figure at 440 V tells you the motor FLA it can handle; for a 400 V line, that typically covers a 3–4 kW motor, depending on the duty cycle. The contactor also carries AC-4 and AC-1 utilisation categories, so it can manage inching/plugging (AC-4) and resistive loads (AC-1) within its thermal current limits. The power circuit is rated for 690 V AC 50/60 Hz, giving headroom for 480 V or 575 V systems, though the AC-3 current rating derates above 440 V — check the thermal curve for higher voltages.

The contactor is IP20 rated (finger-safe terminals per VDE 0106), so it's intended for enclosure or panel mounting — not exposed washdown areas. The preassembled reversing busbar saves panel wiring time, but verify the busbar orientation matches your reversing starter layout before committing the panel. The coil is 100 V DC, so it needs a DC supply or a rectified AC source. The contactor includes one NC auxiliary contact (the '01' in the code), which is typically used for electrical interlocking in the reversing circuit — a standard practice to prevent both contactors from closing simultaneously.

Frequently asked questions

What are the key ratings for the LP2K0901KD?

It is a 3-pole reversing contactor rated AC-3 at ≤440 V, 9 A, with a 100 V DC coil. It also covers AC-4 and AC-1 categories. The power circuit is rated for 690 V AC 50/60 Hz. It includes one NC auxiliary contact.

What is the physical size of the LP2K0901KD?

The dimensions are 57 mm deep, 90 mm wide, and 58 mm tall. It has an IP20 protection rating.

MPN
LP2K0901KD