It carries a 200 V DC coil and one normally closed auxiliary contact, rated for AC-3 duty at 12 A up to 440 V, with additional capability for AC-4 (inching/jogging) and AC-1 (resistive load) applications. The 12 A AC-3 rating at 440 V switches a motor load drawing up to 12 A under full-load starting conditions. The reversing busbar interlock prevents both contactors closing simultaneously.
The contactor measures 90 mm wide, 58 mm high, and 57 mm deep, with IP20 finger-safe protection per VDE 0106 — suitable for enclosed control panels where accidental contact is prevented by the cabinet door. Rated for operation from -25 to 50 °C ambient and storage from -50 to 80 °C, it handles typical industrial environments without derating up to 2000 m altitude. The 200 V DC coil requires a matching DC supply; verify your control voltage matches exactly. The 1 NC auxiliary is wired for status feedback or safety interlock in the reversing circuit.
The TeSys K series is a legacy compact contactor line; the modern replacement family is TeSys Deca or TeSys Giga depending on your current requirements. No direct pin-compatible drop-in is confirmed from the manufacturer, so a panel re-design or adapter bracket may be needed for a like-for-like swap.