Its AC-3 rating at ≤440 V is 12 A, meaning it can switch a three-phase induction motor drawing up to that current under full load.
The utilisation categories cover AC-1 (resistive), AC-3 (squirrel-cage motor starting/running), and AC-4 (plugging/inching). For a motor load, the AC-3 figure governs — 12 A at ≤440 V. The contactor is rated for 690 V AC 50/60 Hz on the power circuit, so it can be used on 400 V or 480 V systems with appropriate derating. The single NC auxiliary contact (1 NC) is built in; no add-on block needed for basic interlocking. IP20 protection (VDE 0106) means it is finger-safe but not sealed — suitable for enclosure-mounted panels, not washdown environments. Flame retardance meets UL 94 V1 and NF F 16-101/102, which is relevant for rail and industrial compliance.