Skip to main content
Schneider Electric LP2K1201UD3 — Contactors

Schneider TeSys K LP2K1201UD3 Reversing Contactor, 3P, 12A A

MPNLP2K1201UD3
Obsolete

Schneider Electric TeSys K reversing contactor, LP2K1201UD3, 3P, AC-3 12A at 440V, 250V DC coil, 1 NC auxiliary, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LP2K1201UD3 — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationMotor control Resistive load
LP2K1201UD3 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3 AC-4 AC-1
LP2K1201UD3 — Contacts & Poles
ParameterValue
Pole configuration3P
LP2K1201UD3 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Shocks contactor opened, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on X axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LP2K1201UD3 — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

The LP2K1201UD3 is a TeSys K reversing contactor, 3P, AC-3 ≤ 440 V 12 A, 250 V DC coil, 1 NC. The 1 NC auxiliary contact is wired into the opposite-direction coil circuit to block simultaneous engagement, a standard safety practice for reversing starters.

AC-3 rating is 12 A at 440 V. AC-4 and AC-1 ratings also apply. IP20 per VDE 0106. The 2000 m altitude rating without derating means it works at most industrial sites; above that, you'd need to factor in air-density effects on arc extinction. Mechanical robustness is specified for shock and vibration per IEC 60068-2-27 and -6 — it holds closed through 15 Gn shocks on the Z axis, and stays open through 10 Gn. That's enough for general industrial machinery but not for extreme off-road or naval applications.

There is no official L* successor listed in the evidence, so a direct drop-in replacement isn't confirmed. If you're designing a new panel or replacing a failed unit, the practical move is to cross-reference the TeSys K family for a current-production reversing contactor with the same coil voltage (250 V DC), pole count (3P), and AC-3 rating (12 A). The physical footprint and mounting pattern of the TeSys K series are consistent, so a newer TeSys K variant is the first place to look. V1 flame retardance per UL 94 and NF F 16-101/102. Protective treatment per IEC 60068 and DIN 50016. IP20 per VDE 0106.

Frequently asked questions

What are the key specifications of the LP2K1201UD3?

It is a 3-pole reversing contactor rated AC-3 12 A at 440 V, with a 250 V DC coil and 1 NC auxiliary contact. It handles AC-4 and AC-1 loads, operates on power circuits up to 690 V AC, and carries IP20 finger-safe protection. Dimensions are 90 mm wide, 58 mm high, 57 mm deep.

MPN
LP2K1201UD3