Schneider Electric LRD3133

Schneider Electric LRD3133

MPNLRD3133
Obsolete

TeSys Deca thermal overload relays - 9...13 A - class 10A

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

LRD3133 key specifications
ParameterValue
Control typeRed push-button stop Blue push-button reset
Network typeDC AC
Product or component typeDifferential thermal overload relay
Climatic withstandIACS E10
VoltagePower circuit 600 V CSA Power circuit 600 V UL Power circuit 690 V IEC 60947-4-1
[Ue] rated operational voltage690 V AC 0...400 Hz power circuit IEC 60947-4-1
[Uimp] rated impulse withstand voltage6 kV
Permissible current0.95 A 380 V AC-15 signalling circuit 0.06 A 440 V DC-13 signalling circuit
[Ith] conventional free air thermal current5 A signalling circuit
Network frequency0...400 Hz
Phase failure sensitivityTripping current 130 % of Ir on two phase, the last one at 0
IP degree of protectionIP20 conforming to IEC 60529

All specifications

LRD3133 additional specifications
ParameterValue
Mounting supportPlate, with specific accessories Rail, with specific accessories Under contactor
Connections - terminalsPower circuit EverLink BTR screw connectors 1 0.002...0.05 in² (1...35 mm²) flexible without cable end Power circuit EverLink BTR screw connectors 1 0.002...0.05 in² (1...35 mm²) flexible with cable end Power circuit EverLink BTR screw connectors 1 0.002...0.05 in² (1...35 mm²) solid without cable end Control circuit spring terminals 1 0.002...0.004 in² (1...2.5 mm²) solid without cable end Control circuit spring terminals 1 0.002...0.004 in² (1...2.5 mm²) flexible without cable end
Depth4.8 in (123 mm)
Width2.2 in (55 mm)
Height2.8 in (70 mm)
StandardsEN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 UL 60947-5-1 CSA C22.2 No 60947-4-1 CSA C22.2 No 60947-5-1 EN 50495
RangeTeSys
Category22347-CONTACTOR,D-LINE,OVERLOADS-NEW
Flame retardanceV1 conforming to UL 94
Device short nameLRD
Relay applicationMotor protection
Tightening torquePower circuit 44.3 lbf.in (5 N.m) EverLink BTR screw connectors
Tripping threshold1.14 +/- 0.06 Ir IEC 60947-4-1
Dielectric strength1.89 kV 50 Hz IEC 60947-1
Mechanical robustnessShocks15 Gn for 11 ms IEC 60068-2-7 Vibrations4 gn IEC 60068-2-6
Associated fuse rating4 A gG for signalling circuit 4 A BS for signalling circuit
Thermal overload classClass 10A IEC 60947-4-1
Temperature compensation-4...140 °F (-20...60 °C)
Auxiliary contact composition1 NO + 1 NC
Ambient air temperature for storage-76...158 °F (-60...70 °C)
Thermal protection adjustment range9...13 A
Ambient air temperature for operation-4...140 °F (-20...60 °C) without derating IEC 60947-4-1