Schneider Electric LT4730BA
MPNLT4730BA
Active
Electronic over current relays, TeSys LT47, automatic, 3 to 30A, 24VAC/DC
$36.83Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Control type | automatic: reset |
| Product or component type | Electronic overcurrent relay |
| Supply voltage | 24 V AC 24 V DC |
| Voltage | Power circuit: 600 V AC conforming to CSA Power circuit: 600 V AC conforming to UL Power circuit: 690 V AC conforming to IEC 60947-4-1 |
| [Uimp] rated impulse withstand voltage | 6 kV |
| [Ith] conventional free air thermal current | 3 A for signalling circuit |
| Network frequency | 50...60 Hz |
| IP degree of protection | IP20 conforming to IEC 60529 IP20 conforming to VDE 0106 |
| Mounting support | Rail |
| Connections - terminals | Signalling circuit: screw clamp terminals 1 1...2.5 mm² - cable stiffness: flexible with cable end Signalling circuit: screw clamp terminals 1 1...2.5 mm² - cable stiffness: flexible without cable end Signalling circuit: screw clamp terminals 2 1...2.5 mm² - cable stiffness: flexible with cable end Signalling circuit: screw clamp terminals 2 1...2.5 mm² - cable stiffness: flexible without cable end |
| Operating altitude | 2000 m |
| Depth | 77.2 mm |
All specifications
| Parameter | Value |
|---|---|
| Width | 71 mm |
| Height | 70.3 mm |
| Product weight | 0.192 kg |
| Standards | IEC 60255-6 IEC 60947 |
| Range | TeSys |
| Time range | 1...120 s - control type R-time 0.3...30 s - control type O-time |
| Local signalling | 1 LED (green) 1 LED (red) |
| Device short name | LT47 |
| Relay application | Locked rotor, mechanical jamming I > 3 x Isetting Overload Imax > Isetting Sensitivity to phase failure |
| Tightening torque | Signalling circuit: 1.7 N.m M3.5 |
| Device application | Protection |
| Tripping threshold | 3...25 A |
| Dielectric strength | 2 kV at 50 Hz conforming to IEC 60255-5 |
| Protective treatment | TH conforming to IEC 60068 |
| Mechanical robustness | Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7 Vibrations: 4 gn conforming to IEC 60068-2-6 |
| Associated fuse rating | 3 A gG for signalling circuit 3 A BS for signalling circuit |
| Auxiliary contact composition | 1 NO + 1 NC |
| Electromagnetic compatibility | Resistance to electrostatic discharge: 8 kV in open air conforming to IEC 61000-4-2 Resistance to electrostatic discharge: 6 kV in direct mode conforming to IEC 61000-4-2 Conducted emission: class A conforming to EN 55011 Immunity to electromagnetic interference: 10 V/m conforming to IEC 61000-4-3 Immunity to fast transients: 2 kV conforming to IEC 61000-4-4 Surge withstand: 6 kV conforming to IEC 61000-4-5 Conducted HF disturbances: 10 V conforming to IEC 61000-4-6 |
| Ambient air temperature for storage | -30...80 °C |
| Thermal protection adjustment range | 3...30 A |
| Ambient air temperature for operation | -25...60 °C without derating conforming to IEC 60947-4-1 |
MPN