Skip to main content
Schneider Electric LTMTMFM

Schneider Electric LTMTMFM

MPNLTMTMFM
Active

Motor Management main unit, TeSys Tera, Modbus, 4 DI and 3 DO, supply 100-240VAC/DC

$500.00Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LTMTMFM key specifications
ParameterValue
ProtocolModbus 2-wire RS 485 1...247 1.2...19.2 kbit/s, terminal block 2 shielded twisted pairs
Metering typeThermal memory Line, phase and average current Line to line and average voltage Motor temperature input Ground fault current Ig Active and reactive power Active and reactive energy Frequency Total voltage harmonic distortion THD (V) Total voltage harmonic distortion THD (U) Total current harmonic distortion THD (I) Phase sequence
Protection typeOverload protection Stalled rotor Locked rotor Short-circuit Undercurrent Overcurrent Current unbalance Phase reversal Phase loss Earth fault protection internal Earth fault protection external Excessive starting time Max number of start Undervoltage Overvoltage Voltage unbalance Underfrequency Overfrequency Reacceleration Temperature protection Analog input protection Communication failure Fail to stop Under power Over power Power factor variation Anti-backspin timer Block output DI interlock protection
Product or component typeMotor controller
Contacts type and composition1 NO + 1 NC fault signal 3 NO
Network and machine diagnosis typeMotor statistics Motor status Event recording Running hours counter/operating time Number of starts and stops Running hours /stop hours counter Start curve showing motor start record Pre-alarms Trip history information Alarm counters
Supply voltage limits85...265 V AC/DC
Short-circuit withstand100 kA
Supply voltage100...240 V AC/DC 50/60 Hz
Voltage250 V AC IEC 60185
[Uimp] rated impulse withstand voltage4 kV
Load current10 A 250 V AC/DC 5 A 30 V DC

All specifications

LTMTMFM additional specifications
ParameterValue
Input current3 mA 100...240 V
Current consumption8...62.8 mA
Current state 0 guaranteedDigital input 0...12 V 5 mA 10 ms
Current state 1 guaranteedDigital input 85...265 V 5 mA 10 ms
Permissible power480 VA AC-15), Ie = 2 A, 500000 cycles output) 30 W DC-13), Ie = 1.25 A, 500000 cycles output)
Maximum output switching frequency2 Hz
IP degree of protectionIP20
Communication port protocolModbus RTU
Connection pitch0.3 in (7.5 mm) for supply voltage 0.2 in (5.0 mm) for others
Connections - terminalsControl circuit connector 1 0.0003...0.004 in² (0.2...2.5 mm²) AWG 24...AWG 14)flexible without cable end Control circuit connector 2 0.0003...0.002 in² (0.2...1.5 mm²) AWG 24...AWG 14)flexible without cable end Control circuit connector 1 0.0004...0.004 in² (0.25...2.5 mm²) AWG 24...AWG 14)flexible with ferrule with cable end Control circuit connector 2 0.0003...0.002 in² (0.2...1.5 mm²) AWG 24...AWG 14)flexible with ferrule with cable end Control circuit connector 1 0.0004...0.004 in² (0.25...2.5 mm²) AWG 24...AWG 14)flexible stranded with cable end Control circuit connector 2 0.0003...0.002 in² (0.2...1.5 mm²) AWG 24...AWG 14)flexible stranded with cable end Control circuit connector 1 0.0003...0.004 in² (0.2...2.5 mm²) AWG 24...AWG 14)solid with cable end Control circuit connector 2 0.0003...0.002 in² (0.2...1 mm²) AWG 24...AWG 14)solid with cable end
Pollution degree3
Operating altitude<= 6561.68 ft (2000 m) without derating
Depth3.5 in (90 mm)
Width4.4 in (112 mm)
Height1.8 in (45 mm)
StandardsEN/IEC 60947-4-1 UL/CSA 60947-4-1
RangeTeSys
CategoryUS10I1222335
Web servicesWeb server
Fire resistance1202 °F (650 °C) IEC 60947-1 1760 °F (960 °C) UL 94
Device short nameLTMT
Tightening torqueControl circuit 4.4 lbf.in (0.5 N.m) flat 0.1 in (3 mm)
Device applicationEquipment monitoring and control
Logic input number4
Measurement accuracy1 % current 0.3...3 A) 1 % current 2.5...25 A) 3 % current 7...70 A) 3 % current 10...100 A) 1 % voltage 110...690 V) +/- 2.5 % earth fault current external measurement +/- 3...5 % earth fault current internal measurement current > 0.03 A in the 0.3...3 A range) +/- 3...5 % earth fault current internal measurement current > 0.25 A in the 2.5...25 A range) +/- 3...5 % earth fault current internal measurement current > 0.7 A in the 7...70 A range) +/- 3...5 % earth fault current internal measurement current > 1 A in the 10...100 A range) +/- 2 % Temperature +/- 2 % THD measurement +/- 3...6 % power factor +/- 2...5 % active and reactive energy +/- 30 min/year internal clock
Overvoltage categoryIII
Mechanical robustnessVibrations mounted on symmetrical rail1 Gn, 5...300 Hz EN/IEC 60068-2-27 Vibrations plate mounted4 Gn, 5...300 Hz EN/IEC 60068-2-6 Shocks half sine wave acceleration15 Gn for 11 ms EN/IEC 60068-2-27
Associated fuse rating0.5 A gG control circuit
Maximum operating rate1800 cyc/h
Ambient air temperature for storage-40...176 °F (-40...80 °C)
Ambient air temperature for operation-4...158 °F (-20...70 °C)
MPN