| Parameter | Value |
|---|---|
| Range of product | TeSys Ultra |
| Voltage withstand | 6 kV IEC 60947-6-2 |
| Voltage insulation | 690 V IEC 60947-6-2 600 V UL 60947-4-1 600 V CSA C22.2 No 60947-4-1 |
| Phase failure sensitivity | Yes |
| Utilization category | AC-43 AC-44 AC-41 |
| Shock | 10 gn power poles open IEC 60068-2-27 15 gn power poles closed IEC 60068-2-27 |
| Altitude max | 6561.68 ft (2000 m) |
| Non-Dissipating shock wave | 1 kV serial mode IEC 60947-6-2 2 kV common mode IEC 60947-6-2 |
| Depth | 60.96 |
| Width | 45.72 |
| Height | 66.04 |
| Standards | EN 60947-6-2 IEC 60947-6-2 UL 60947-4-1, with phase barrier CSA C22.2 No 60947-4-1, with phase barrier |
All specifications
| Parameter | Value |
|---|---|
| Range | TeSys |
| Power | 90 |
| IP rating | IP20 front panel and wired terminals IEC 60947-1 IP20 other faces IEC 60947-1 IP40 front panel outside connection zone IEC 60947-1 |
| Load_type | 3-phase motor self-cooled |
| Fixing_mode | Plug-in (front face) |
| Frequency | 40 |
| Package_type | PCE |
| Coil voltage | 48 |
| Resistance | 1760 °F (960 °C) parts supporting live components IEC 60695-2-12 1202 °F (650 °C) IEC 60695-2-12 |
| Heat dissipation | 2 W control circuit with LUB12 3 W control circuit with LUB32 3 W control circuit with LUB38 |
| Application_type | Motor control Motor protection |
| Supply voltage | 690 |
| Device short name | LUCA |
| Operating time | 35 ms opening with LUB12 control circuit 35 ms opening with LUB32 control circuit 35 ms opening with LUB38 control circuit 60 ms closing with LUB12 control circuit 60 ms closing with LUB32 control circuit 60 ms closing with LUB38 control circuit |
| Compatibility code | LUCA |
| Tripping threshold | 14.2 x Ir +/- 20 % |
| Switching current | 0.15 |
| Storage temperature | -40...185 °F (-40...85 °C) |
| Protective treatment | TH IEC 60068 |
| Thermal_overload_class | Class 10 40...60 Hz -13...158 °F (-25...70 °C) IEC 60947-6-2 Class 10 40...60 Hz -13...158 °F (-25...70 °C) UL 508 |
| Immunity to microbreaks | 3 ms |
| Main function available | Manual reset Protection against phase failure and phase imbalance Protection against overload and short-circuit Earth fault protection |
| Safe separation of circuit | 400 V SELV between the control and auxiliary circuits IEC 60947-1 400 V SELV between the control or auxiliary circuit and the main circuit IEC 60947-1 |
| Product specific application | Basic protection requirements for motor starters: overload and short-circuit |
| Main_product_or_component_type | Standard control unit |
| Immunity to radioelectric fields | 10 V IEC 61000-4-6 |
| Operating temperature | -13 |
| Ordering and shipping details (Category) | US10I1122397 |