Schneider Electric LV426206
MPNLV426206
Obsolete
circuit breaker Compact NSXm 80A 3P 25kA at 380/415V(IEC) EverLink lug
$113.08 – $231.64Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →Specifications
| Parameter | Value |
|---|---|
| Control type | Toggle |
| Network type | AC |
| Protection type | L : for overload protection (thermal) I : for short-circuit protection (magnetic) |
| Range of product | ComPact NSXm |
| Product or component type | Circuit breaker |
| Long-time protection delay adjustment type tr | Fixed |
| Long-time pick-up adjustment type ir (thermal protection) | Adjustable |
| Voltage | 800 V AC 50/60 Hz |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Current | 80 A at 40 °C |
| [Ics] rated service short-circuit breaking capacity | 50 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
All specifications
| Parameter | Value |
|---|---|
| [Icu] rated ultimate short-circuit breaking capacity | 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
| Network frequency | 50/60 Hz |
| Poles | 3P |
| Protected poles description | 3D |
| Utilisation category | Category A |
| IK degree of protection | IK07 conforming to IEC 62262 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| Mounting support | Plate DIN rail |
| Circuit breaker mounting mode | By screws Clip-on |
| Connection pitch | 35 mm with spreaders 27 mm without spreaders |
| Connection terminals | 1 Everlink lug wire size 2.5...95 mm², rigid or stranded aluminium/copper 1 Everlink lug wire size 2.5...70 mm², flexible copper |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Relative humidity | 0...95 % |
| Operating altitude | 0...2000 m without derating 2000...5000 m with derating |
| Color | Grey (RAL 7016) |
| Depth | 80 mm |
| Width | 81 mm |
| Height | 137 mm |
| Product weight | 1.06 kg |
| Electrical durability | 10000 cycles at 440 V In 20000 cycles at 440 V In/2 5000 cycles at 690 V In 10000 cycles at 690 V In/2 |
| Mechanical durability | 20000 cycles |
| Standards | EN/IEC 60947 |
| Range | ComPact |
| 9 mm pitches | 9 module |
| Trip unit name | TM-D |
| Trip unit rating | 80 A at 40 °C |
| Device short name | NSXm 80B |
| Safety category | B 25 kA 415 V AC |
| Device application | Distribution Protection |
| Trip unit technology | Thermal-magnetic |
| Earth-leakage protection | Without |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Trip unit protection functions | LI |
| Ambient air temperature for storage | -50...85 °C |
| Ambient air temperature for operation | -25...70 °C |
| [Im] magnetic protection pick-up range | 1000 A |
| Number of slots for electrical auxiliaries | 1 slot(s) for auxiliary switch OF 1 slot(s) for alarm switch SD 1 slot(s) for voltage release MN or MX |
| [Ir] long-time protection pick-up adjustment range | 0.7...1 x In |
MPN