Skip to main content
Schneider Electric LV429960

Schneider Electric LV429960

MPNLV429960
Obsolete

Circuit breaker, VigiComPact NSX100B, 25kA/415VAC, TM-D trip unit 100A, add-on Vigi MH module, 4P 4d

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LV429960 key specifications
ParameterValue
Control typeToggle
Network typeAC
Protection typeL : for overload protection (thermal) I : for short-circuit protection (magnetic)
Range of productComPact NSX100...250
Product or component typeCircuit breaker with Vigi add-on
Long-time protection delay adjustment type trFixed
Short-time protection delay adjustment type tsdFixed
Short-time protection pick-up adjustment type isdFixed
Earth-leakage protection sensitity adjustment type iδnAdjustable 5 settings
Earth-leakage protection time delay adjustement type δtAdjustable 4 settings
Long-time pick-up adjustment type ir (thermal protection)Adjustable
Voltage800 V AC 50/60 Hz

All specifications

LV429960 additional specifications
ParameterValue
[Ue] rated operational voltage440 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
Line rated current100 A 104 °F (40 °C)
[Ics] rated service short-circuit breaking capacity20 kA 440 V AC 50/60 Hz IEC 60947-2 25 kA 380/415 V AC 50/60 Hz IEC 60947-2 40 kA 220/240 V AC 50/60 Hz IEC 60947-2 7.5 kA 500 V AC 50/60 Hz IEC 60947-2
[Icu] rated ultimate short-circuit breaking capacity15 kA Icu 500 V AC 50/60 Hz IEC 60947-2 20 kA Icu 440 V AC 50/60 Hz IEC 60947-2 25 kA Icu 380/415 V AC 50/60 Hz IEC 60947-2 40 kA Icu 220/240 V AC 50/60 Hz IEC 60947-2
Network frequency50/60 Hz
Poles4P
Protected poles description4t
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to IEC 62262
IP degree of protectionIP40 conforming to IEC 60529
Mounting supportBackplate
Circuit breaker mounting modeFixed
Connection pitch1.4 in (35 mm)
Upside connectionFront
Downside connectionFront
Pollution degree3 IEC 60664-1
Relative humidity0...95 %
Operating altitude0...6561.68 ft (0...2000 m) without derating 2000 m...5000 m with derating
Electrical shock protection classClass II
Depth3.4 in (86 mm)
Width5.5 in (140 mm)
Height9.3 in (236 mm)
Electrical durability10000 cycles 690 V In 20000 cycles 690 V In/2 30000 cycles 440 V In 50000 cycles 440 V In/2
Mechanical durability50000 cycles
StandardsEN/IEC 60947
RangeComPact
Category01101-NF..E COMPACT NS IEC CIRCUIT BREAKERS, SWITCHES & MCP'S
Trip unit nameTM-D
Neutral positionLeft
Trip unit rating100 A 104 °F (40 °C)
Device short nameVigiCompact NSX100B
Safety categoryB 25 kA 415 V AC
Device applicationDistribution
Overvoltage categoryClass II
Trip unit technologyThermal-magnetic
Earth-leakage protectionWith
Suitability for isolationYes EN/IEC 60947-2
Neutral protection settings1 x Ir 4t)
Earth-leakage protection classClass A
Trip unit protection functionsLI
Earth-leakage add-on module nameMH
Ambient air temperature for storage-58...185 °F (-50...85 °C)
Ambient air temperature for operation-13...158 °F (-25...70 °C)
Number of slots for electrical auxiliaries6
[Tr] Long-Time protection delay adjustment range120...400 s 1.5 x In 15 s 6 x Ir
[Ir] long-time protection pick-up adjustment range0.7...1 x In
[Isd] short-time protection pick-up adjustment range800 A
[IΔn] earth-leakage protection sensitivity adjustment range0.03...10 A
MPN