Skip to main content
Schneider Electric LV430480

Schneider Electric LV430480

MPNLV430480
Obsolete

LV430480 - TRIP UNIT by TELEMECANIQUE

$1,237.06Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LV430480 key specifications
ParameterValue
Network typeAC
Protection typeL : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection
Range of productComPact NSX100...250
Product or component typeTrip unit
Long-time protection delay adjustment type trFixed
Short-time protection delay adjustment type tsdFixed
Short-time protection pick-up adjustment type isdAdjustable 9 settings
Instantaneous protection pick-up adjustment type iiFixed
Long-time pick-up adjustment type ir (thermal protection)Adjustable 9 settings
[Ue] rated operational voltage690 V AC 50/60 Hz
Trip unit rated current160 A 104 °F (40 °C)
Network frequency50/60 Hz

All specifications

LV430480 additional specifications
ParameterValue
Poles4P
Protected poles description4t 3t + N/2 3t
StandardsUL 508 EN/IEC 60947-2
RangeComPact
CategoryUS10DE201101
Thermal memory20 minutes before and after tripping
Trip unit nameMicroLogic 2.2
Local signallingFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
Neutral positionLeft
Device applicationDistribution
Trip unit technologyElectronic
Earth-leakage protectionWithout
Neutral protection settings0.5 x Ir 3t + N/2) 1 x Ir 4t) No protection 3t)
Trip unit protection functionsLSoI
Zone selective interlocking ZSIWithout
Ambient air temperature for storage-58...185 °F (-50...85 °C)
Ambient air temperature for operation-13...158 °F (-25...70 °C)
[Tr] Long-Time protection delay adjustment range11 s 7.2 x Ir 16 s 6 x Ir 400 s 1.5 x Ir
[Ir] long-time protection pick-up adjustment range63...160 A
[tsd] short-time protection delay adjustment range0.02 s
[Isd] short-time protection pick-up adjustment range1.5...10 x Ir
[Ii] instantaneous protection pick-up adjustment range2400 A
MPN