Specifications

LV430490 key specifications
ParameterValue
Display typeLCD display
Network typeAC
Protection typeL : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection
Range of productComPact NSX100...250
Type of measurementAmmeter
Product or component typeTrip unit
Long-time protection delay adjustment type trAdjustable
Short-time protection delay adjustment type tsdAdjustable
Short-time protection pick-up adjustment type isdAdjustable 9 settings
Instantaneous protection pick-up adjustment type iiAdjustable
Long-time pick-up adjustment type ir (thermal protection)Adjustable 9 settings
[Ue] rated operational voltage690 V AC 50/60 Hz

All specifications

LV430490 additional specifications
ParameterValue
Trip unit rated current160 A at 40 °C
Network frequency50/60 Hz
Poles3P
Protected poles description3t
Communication of dataMaintenance indicators Protection and alarm settings Demand current and power Energy metering Maximeters/minimeters Time-stamped histories and event tables Instantaneous and demand values Power quality
StandardsUL 508 EN/IEC 60947-2
RangeComPact
Thermal memory20 minutes before and after tripping
Trip unit nameMicroLogic 5.2 A
Local signallingFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
Device applicationDistribution
Trip unit technologyElectronic
Earth-leakage protectionWithout
Electrical data recordingMaintenance indicators
Trip unit protection functionsLSI
Zone selective interlocking ZSIWith
Ambient air temperature for storage-40...85 °C
Ambient air temperature for operation-25...70 °C
[Tr] Long-Time protection delay adjustment range15...400 s at 1.5 x Ir 0.35...11 s at 7.2 x Ir 0.5...16 s at 6 x Ir
[Ir] long-time protection pick-up adjustment range63...160 A
[tsd] short-time protection delay adjustment range0...0.4 s I²t=off 0.1...0.4 s I²t=on
[Isd] short-time protection pick-up adjustment range1.5...10 x Ir
[Ii] instantaneous protection pick-up adjustment range1.5...15 x In
MPN