Skip to main content
Schneider Electric LV431146

Schneider Electric LV431146

MPNLV431146
Obsolete

Circuit breaker, ComPact NSX250B, 25kA/415VAC, MicroLogic 5.2A trip unit 160A, 3 poles 3d

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LV431146 key specifications
ParameterValue
Control typeToggle
Display typeLCD display
Network typeAC
Protection typeL : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection
Range of productComPact NSX100...250
Type of measurementAmmeter
Product or component typeCircuit breaker
Long-time protection delay adjustment type trAdjustable
Short-time protection delay adjustment type tsdAdjustable
Short-time protection pick-up adjustment type isdAdjustable
Instantaneous protection pick-up adjustment type iiAdjustable
Long-time pick-up adjustment type ir (thermal protection)Adjustable

All specifications

LV431146 additional specifications
ParameterValue
Voltage800 V AC 50/60 Hz
[Ue] rated operational voltage690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
Current160 A at 40 °C
[Ics] rated service short-circuit breaking capacity20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
[Icu] rated ultimate short-circuit breaking capacity15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Network frequency50/60 Hz
Poles3P
Protected poles description3t
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to IEC 62262
IP degree of protectionIP40 conforming to IEC 60529
Communication of dataTime-stamped histories and event tables Instantaneous and demand values Maintenance indicators Protection and alarm settings Power quality Demand current and power Maximeters/minimeters Energy metering
Mounting supportBackplate
Circuit breaker mounting modeFixed
Connection pitch35 mm
Upside connectionFront
Downside connectionFront
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
Electrical shock protection classClass II
Depth86 mm
Width105 mm
Height161 mm
Electrical durability5000 cycles at 690 V In 10000 cycles at 690 V In/2 10000 cycles at 440 V In 20000 cycles at 440 V In/2
Mechanical durability20000 cycles
StandardsEN/IEC 60947
RangeComPact
Thermal memory20 minutes before and after tripping
Trip unit nameMicroLogic 5.2 A
Local signallingFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
Trip unit rating160 A at 40 °C
Device short nameNSX250B
Safety categoryB 25 kA 415 V AC
Device applicationDistribution
Overvoltage categoryClass II
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Trip unit protection functionsLSI
Zone selective interlocking ZSIWith
Ambient air temperature for storage-40...85 °C
Ambient air temperature for operation-25...70 °C
Number of slots for electrical auxiliaries5 slot(s)
[Tr] Long-Time protection delay adjustment range15...400 s at 1.5 x Ir 0.35...11 s at 7.2 x Ir 0.5...16 s at 6 x Ir
[Ir] long-time protection pick-up adjustment range63...160 A
[tsd] short-time protection delay adjustment range0...0.4 s
[Isd] short-time protection pick-up adjustment range1.5...10 x Ir
[Ii] instantaneous protection pick-up adjustment range1.5...12 x In
MPN