Specifications

LV432701 key specifications
ParameterValue
Control typeToggle
Display typeLCD display
Network typeAC
Protection typeL : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection
Range of productComPact NSX400...630
Type of measurementAmmeter
Product or component typeCircuit breaker
Long-time protection delay adjustment type trAdjustable
Short-time protection delay adjustment type tsdAdjustable
Short-time protection pick-up adjustment type isdAdjustable
Instantaneous protection pick-up adjustment type iiAdjustable
Long-time pick-up adjustment type ir (thermal protection)Adjustable

All specifications

LV432701 additional specifications
ParameterValue
Voltage800 V AC 50/60 Hz
[Ue] rated operational voltage690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
Current400 A at 40 °C
[Ics] rated service short-circuit breaking capacity11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
[Icu] rated ultimate short-circuit breaking capacity85 kA at 240 V AC 50/60 Hz conforming to UL 508 65 kA at 480 V AC 50/60 Hz conforming to UL 508 100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 600 V AC 50/60 Hz conforming to UL 508 20 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Network frequency50/60 Hz
Poles3P
Protected poles description3t
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to IEC 62262
IP degree of protectionIP40 conforming to IEC 60529
Communication of dataMaximeters/minimeters Time-stamped histories and event tables Power quality Maintenance indicators Protection and alarm settings Instantaneous and demand values Demand current and power Energy metering
Mounting supportBackplate
Circuit breaker mounting modeFixed
Connection pitch45 mm
Upside connectionFront
Downside connectionFront
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
Electrical shock protection classClass II
Depth110 mm
Width140 mm
Height255 mm
Product weight6.05 kg
Electrical durability3000 cycles at 690 V In 6000 cycles at 690 V In/2 6000 cycles at 440 V In 12000 cycles at 440 V In/2
Mechanical durability15000 cycles
StandardsEN/IEC 60947
RangeComPact
Thermal memory20 minutes before and after tripping
Trip unit nameMicroLogic 5.3 A
Local signallingFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
Trip unit rating400 A at 40 °C
Device short nameNSX400H
Safety categoryH 70 kA 415 V AC
Device applicationDistribution
Overvoltage categoryClass II
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Trip unit protection functionsLSI
Zone selective interlocking ZSIWith
Ambient air temperature for storage-40...85 °C
Ambient air temperature for operation-25...70 °C
Number of slots for electrical auxiliaries6 slot(s)
[Tr] Long-Time protection delay adjustment range15...400 s at 1.5 x Ir 0.35...11 s at 7.2 x Ir 0.5...16 s at 6 x Ir
[Ir] long-time protection pick-up adjustment range160...400 A
[tsd] short-time protection delay adjustment range0...0.4 s
[Isd] short-time protection pick-up adjustment range1.5...10 x Ir
[Ii] instantaneous protection pick-up adjustment range1.5...12 x In

Product details

Overview

The LV432701 is a Schneider ComPact NSX400H molded case circuit breaker rated 400 A at 40 °C with three poles and an 85 kA breaking capacity at 415 V AC, built for distribution duty on a 690 V AC network. It carries a MicroLogic 5.3 A electronic trip unit providing LSI protection — long-time overload, short-time short-circuit, and instantaneous — with an LCD display for metering and event logs.

MPN
LV432701