Skip to main content
Schneider Electric LV432949

Schneider LV432949 ComPact NSX MCCB, 3-pole, 500 A, 85 kA

MPNLV432949
Obsolete

Schneider LV432949 Compact Nsx — now discontinued, supplied from remaining surplus and broker stock.

$1,969.89Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LV432949 key specifications
ParameterValue
Control typeToggle
Network typeAC
Protection typeI : for short-circuit protection (magnetic)
Range of productComPact NSX400...630
Product or component typeCircuit breaker
Short-time protection delay adjustment type tsdFixed
Short-time protection pick-up adjustment type isdAdjustable 9 settings
Instantaneous protection pick-up adjustment type iiFixed
Voltage800 V AC 50/60 Hz
[Ue] rated operational voltage690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
Current500 A at 65 °C

All specifications

LV432949 additional specifications
ParameterValue
[Ics] rated service short-circuit breaking capacity11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 42 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
[Icu] rated ultimate short-circuit breaking capacity85 kA at 240 V AC 50/60 Hz conforming to UL 508 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 600 V AC 50/60 Hz conforming to UL 508 50 kA at 480 V AC 50/60 Hz conforming to UL 508 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
Network frequency50/60 Hz
Poles3P
Protected poles description3t
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to IEC 62262
IP degree of protectionIP40 conforming to IEC 60529
Mounting supportBackplate
Circuit breaker mounting modeFixed
Connection pitch45 mm
Upside connectionFront
Downside connectionFront
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
Electrical shock protection classClass II
Depth110 mm
Width140 mm
Height255 mm
Product weight6.2 kg
Electrical durability2000 cycles at 690 V In 6000 cycles at 690 V In/2 4000 cycles at 440 V In 8000 cycles at 440 V In/2
Mechanical durability15000 cycles
StandardsEN/IEC 60947
RangeComPact
Trip unit nameMicroLogic 1.3 M
Local signallingFlashing LED (green) for ready to operate
Trip unit rating500 A at 65 °C
Device short nameNSX630N
Safety categoryN 50 kA 415 V AC
Device applicationMotor
Overvoltage categoryClass II
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Trip unit protection functionsI
Zone selective interlocking ZSIWithout
Ambient air temperature for storage-50...85 °C
Ambient air temperature for operation-25...70 °C
Number of slots for electrical auxiliaries6 slot(s)
[Isd] short-time protection pick-up adjustment range2500 A 4000 A 5500 A 6500 A 4500 A 3500 A 5000 A 3000 A 6000 A
[Ii] instantaneous protection pick-up adjustment range6500 A

Product details

Overview

The LV432949 is a Schneider ComPact NSX molded case circuit breaker rated for 3-pole motor duty at 500 A switching current on a 690 V AC supply, carrying an 85 kA ICu breaking capacity at 415 V AC. It ships with a MicroLogic 1.3 M electronic trip unit set to 500 A at 65 °C, providing magnetic short-circuit protection for motor feeders.

The 85 kA ICu at 415 V AC gives headroom for high-fault installations; the MicroLogic 1.3 M trip unit is tuned for motor inrush, not distribution overloads, so size it for the motor full-load current, not the breaker's 500 A maximum.

MPN
LV432949