Skip to main content
Schneider Electric LV433024

Schneider Electric LV433024

MPNLV433024
Obsolete

trip unit Micrologic 2.2M, for Compact NSX 100/160/250 R/HB, LSoI motor protections, electronic, 25 A rating, 3P 3d

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LV433024 key specifications
ParameterValue
Network typeAC
Protection typeL : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection
Range of productComPact NSX100...250
Product or component typeTrip unit
Short-time protection delay adjustment type tsdFixed
Short-time protection pick-up adjustment type isdAdjustable 9 settings
Instantaneous protection pick-up adjustment type iiFixed
Long-time pick-up adjustment type ir (thermal protection)Adjustable 9 settings
[Ue] rated operational voltage690 V AC 50/60 Hz
Trip unit rated current25 A at 65 °C
Network frequency50/60 Hz
Poles3P

All specifications

LV433024 additional specifications
ParameterValue
Protected poles description3t
StandardsEN/IEC 60947-2 UL 508
RangeComPact
Thermal memory20 minutes before and after tripping
Trip unit nameMicroLogic 2.2 M
Local signallingFlashing LED (green) for ready to operate LED 95 % Ith (red) for temperature over set point
Device applicationMotor
Motor tripping class10 5 20
Trip unit technologyElectronic
Earth-leakage protectionWithout
Complementary motor protectionPhase unbalance
Trip unit protection functionsLSoI
Zone selective interlocking ZSIWithout
Ambient air temperature for storage-50...85 °C
Ambient air temperature for operation-25...70 °C
[Tr] Long-Time protection delay adjustment range120 s at 1.5 x Ir for trip class 5 6.5 s at 6 x Ir for trip class 5 5 s at 7.2 x Ir for trip class 5 240 s at 1.5 x Ir for trip class 10 13.5 s at 6 x Ir for trip class 10 10 s at 7.2 x Ir for trip class 10 480 s at 1.5 x Ir for trip class 20 26 s at 6 x Ir for trip class 20 20 s at 7.2 x Ir for trip class 20
[Ir] long-time protection pick-up adjustment range12...25 A
[tsd] short-time protection delay adjustment range0.01 s
[Isd] short-time protection pick-up adjustment range5...13 x Ir
[Ii] instantaneous protection pick-up adjustment range425 A
MPN
LV433024