Skip to main content
Schneider Electric LV433492

Schneider Electric LV433492

MPNLV433492
Obsolete

Circuit breaker, ComPact NSX250HB2, 100kA/690VAC, TMD trip unit 250A, 3 poles 3d

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LV433492 key specifications
ParameterValue
Control typeToggle
Network typeAC
Protection typeL : for overload protection (thermal) I : for short-circuit protection (magnetic)
Range of productComPact NSX100...250
Product or component typeCircuit breaker
Long-time protection delay adjustment type trFixed
Short-time protection delay adjustment type tsdFixed
Short-time protection pick-up adjustment type isdAdjustable
Long-time pick-up adjustment type ir (thermal protection)Adjustable
Voltage800 V AC 50/60 Hz
[Ue] rated operational voltage690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV

All specifications

LV433492 additional specifications
ParameterValue
Line rated current250 A 104 °F (40 °C)
[Ics] rated service short-circuit breaking capacity100 kA 500 V AC 50/60 Hz IEC 60947-2 100 kA 525 V AC 50/60 Hz IEC 60947-2 100 kA 660/690 V AC 50/60 Hz IEC 60947-2
[Icu] rated ultimate short-circuit breaking capacity100 kA Icu 500 V AC 50/60 Hz IEC 60947-2 100 kA Icu 525 V AC 50/60 Hz IEC 60947-2 100 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2
Network frequency50/60 Hz
Poles3P
Protected poles description3t
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to IEC 62262
IP degree of protectionIP40 conforming to IEC 60529
Mounting supportBackplate
Circuit breaker mounting modeFixed
Connection pitch1.4 in (35 mm)
Upside connectionFront
Downside connectionFront
Pollution degree3 IEC 60664-1
Relative humidity0...95 %
Operating altitude0...6561.68 ft (0...2000 m) without derating 2000 m...5000 m with derating
Electrical shock protection classClass II
Depth3.4 in (86 mm)
Width4.1 in (105 mm)
Height6.3 in (161 mm)
Electrical durability5000 cycles 690 V In 10000 cycles 690 V In/2 10000 cycles 440 V In 20000 cycles 440 V In/2
Mechanical durability20000 cycles
StandardsEN/IEC 60947
RangeComPact
CategoryUS10DE201101
Trip unit nameTM-D
Trip unit rating250 A 104 °F (40 °C)
Device short nameNSX250HB2
Safety categoryHB2 100 kA 690 V AC
Device applicationDistribution
Overvoltage categoryClass II
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes EN/IEC 60947-2
Trip unit protection functionsLI
Ambient air temperature for storage-58...185 °F (-50...85 °C)
Ambient air temperature for operation-13...158 °F (-25...70 °C)
Number of slots for electrical auxiliaries5
[Tr] Long-Time protection delay adjustment range120...400 s 1.5 x In 15 s 6 x Ir
[Ir] long-time protection pick-up adjustment range0.7...1 x In
[Isd] short-time protection pick-up adjustment range5...10 x In
MPN