Specifications

LV433628 key specifications
ParameterValue
Control typeToggle
Display typeLCD display
Network typeAC
Protection typeL : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection G : for ground fault protection
Range of productComPact NSX400...630
Type of measurementEnergy meter
Product or component typeCircuit breaker
Long-time protection delay adjustment type trAdjustable
Short-time protection delay adjustment type tsdAdjustable 5 settings
Short-time protection pick-up adjustment type isdAdjustable
Ground-fault protection pick-up adjustment type igAdjustable 9 settings
Instantaneous protection pick-up adjustment type iiAdjustable

All specifications

LV433628 additional specifications
ParameterValue
Ground-fault protection time delay adjustment type tgAdjustable
Long-time pick-up adjustment type ir (thermal protection)Adjustable 9 settings
Voltage800 V AC 50/60 Hz
[Ue] rated operational voltage690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
Line rated current400 A 104 °F (40 °C)
[Ics] rated service short-circuit breaking capacity85 kA 500 V AC 50/60 Hz IEC 60947-2 80 kA 525 V AC 50/60 Hz IEC 60947-2 75 kA 660/690 V AC 50/60 Hz IEC 60947-2
[Icu] rated ultimate short-circuit breaking capacity85 kA Icu 500 V AC 50/60 Hz IEC 60947-2 80 kA Icu 525 V AC 50/60 Hz IEC 60947-2 75 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2
Network frequency50/60 Hz
Poles3P
Protected poles description3t
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to IEC 62262
IP degree of protectionIP40 conforming to IEC 60529
Communication of dataProtection and alarm settings Time-stamped histories and event tables Energy metering Power quality Maximeters/minimeters Instantaneous and demand values Maintenance indicators Demand current and power
Mounting supportBackplate
Circuit breaker mounting modeFixed
Connection pitch1.8 in (45 mm)
Upside connectionFront
Downside connectionFront
Pollution degree3 IEC 60664-1
Relative humidity0...95 %
Operating altitude0...6561.68 ft (0...2000 m) without derating 2000 m...5000 m with derating
Electrical shock protection classClass II
Depth4.3 in (110 mm)
Width5.5 in (140 mm)
Height10.04 in (255 mm)
Electrical durability3000 cycles 690 V In 6000 cycles 690 V In/2 6000 cycles 440 V In 12000 cycles 440 V In/2
Mechanical durability15000 cycles
StandardsEN/IEC 60947
RangeComPact
CategoryUS10DE201101
Thermal memory20 minutes before and after tripping
Trip unit nameMicroLogic 6.3 E
Local signallingFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
Trip unit rating400 A 104 °F (40 °C)
Device short nameNSX400HB1
Safety categoryHB1 75 kA 690 V AC
Device applicationDistribution
Overvoltage categoryClass II
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes EN/IEC 60947-2
Trip unit protection functionsLSIG
Zone selective interlocking ZSIWith
Ambient air temperature for storage-40...185 °F (-40...85 °C)
Ambient air temperature for operation-13...158 °F (-25...70 °C)
Number of slots for electrical auxiliaries6
[Tr] Long-Time protection delay adjustment range15...400 s 1.5 x Ir 0.35...11 s 7.2 x Ir 0.5...16 s 6 x Ir
[Ir] long-time protection pick-up adjustment range160...400 A
[tsd] short-time protection delay adjustment range0...0.4 s
[Isd] short-time protection pick-up adjustment range1.5...12 x In
[Ig] ground-fault protection pick-up adjustment range0.4...1 x In In = 40 A 0.2...1 x In In > 40 A Ig enable on/off
[Ii] instantaneous protection pick-up adjustment range1.5...12 x In
[Tg] Ground-Fault protection time delay adjustment range0...0.4 s I²t=off 0.1...0.4 s I²t=on