Skip to main content
Schneider Electric LV433706

Schneider Electric LV433706

MPNLV433706
Obsolete

LV433706 - CIRCUIT BREAKER by SQUARE D

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LV433706 key specifications
ParameterValue
Control typeToggle
Display typeLCD display
Network typeAC
Protection typeL : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection G : for ground fault protection
Range of productComPact NSX400...630
Type of measurementEnergy meter
Product or component typeCircuit breaker
Long-time protection delay adjustment type trAdjustable
Short-time protection delay adjustment type tsdAdjustable 5 settings
Short-time protection pick-up adjustment type isdAdjustable
Ground-fault protection pick-up adjustment type igAdjustable 9 settings
Instantaneous protection pick-up adjustment type iiAdjustable

All specifications

LV433706 additional specifications
ParameterValue
Ground-fault protection time delay adjustment type tgAdjustable
Long-time pick-up adjustment type ir (thermal protection)Adjustable 9 settings
Voltage800 V AC 50/60 Hz
[Ue] rated operational voltage690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
Line rated current630 A 104 °F (40 °C)
[Ics] rated service short-circuit breaking capacity200 kA 220/240 V AC 50/60 Hz IEC 60947-2 200 kA 380/415 V AC 50/60 Hz IEC 60947-2 200 kA 440 V AC 50/60 Hz IEC 60947-2 80 kA 500 V AC 50/60 Hz IEC 60947-2 16 kA 525 V AC 50/60 Hz IEC 60947-2 12 kA 660/690 V AC 50/60 Hz IEC 60947-2
[Icu] rated ultimate short-circuit breaking capacity200 kA Icu 220/240 V AC 50/60 Hz IEC 60947-2 200 kA Icu 380/415 V AC 50/60 Hz IEC 60947-2 200 kA Icu 440 V AC 50/60 Hz IEC 60947-2 80 kA Icu 500 V AC 50/60 Hz IEC 60947-2 65 kA Icu 525 V AC 50/60 Hz IEC 60947-2 45 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2
Network frequency50/60 Hz
Poles3P
Protected poles description3t
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to IEC 62262
IP degree of protectionIP40 conforming to IEC 60529
Communication of dataTime-stamped histories and event tables Maximeters/minimeters Protection and alarm settings Power quality Demand current and power Maintenance indicators Instantaneous and demand values Energy metering
Mounting supportBackplate
Circuit breaker mounting modeFixed
Connection pitch1.8 in (45 mm)
Upside connectionFront
Downside connectionFront
Pollution degree3 IEC 60664-1
Relative humidity0...95 %
Operating altitude0...6561.68 ft (0...2000 m) without derating 2000 m...5000 m with derating
Electrical shock protection classClass II
Depth4.3 in (110 mm)
Width5.5 in (140 mm)
Height10.04 in (255 mm)
Electrical durability2000 cycles 690 V In 6000 cycles 690 V In/2 4000 cycles 440 V In 8000 cycles 440 V In/2
Mechanical durability15000 cycles
StandardsEN/IEC 60947
RangeComPact
CategoryUS10DE201101
Thermal memory20 minutes before and after tripping
Trip unit nameMicroLogic 6.3 E
Local signallingFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
Trip unit rating630 A 104 °F (40 °C)
Device short nameNSX630R
Safety categoryR 200 kA 415 V AC
Device applicationDistribution
Overvoltage categoryClass II
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes EN/IEC 60947-2
Trip unit protection functionsLSIG
Zone selective interlocking ZSIWith
Ambient air temperature for storage-40...185 °F (-40...85 °C)
Ambient air temperature for operation-13...158 °F (-25...70 °C)
Number of slots for electrical auxiliaries6
[Tr] Long-Time protection delay adjustment range15...400 s 1.5 x Ir 0.35...11 s 7.2 x Ir 0.5...16 s 6 x Ir
[Ir] long-time protection pick-up adjustment range250...630 A
[tsd] short-time protection delay adjustment range0...0.4 s
[Isd] short-time protection pick-up adjustment range1.5...11 x In
[Ig] ground-fault protection pick-up adjustment range0.4...1 x In In = 40 A 0.2...1 x In In > 40 A Ig enable on/off
[Ii] instantaneous protection pick-up adjustment range1.5...11 x In
[Tg] Ground-Fault protection time delay adjustment range0...0.4 s I²t=off 0.1...0.4 s I²t=on
MPN
LV433706