Skip to main content
Schneider Electric LV433707

Schneider Electric LV433707

MPNLV433707
Obsolete

Circuit breaker, ComPact NSX630R, 200kA/415VAC, MicroLogic 6.3E trip unit 630A, 4 poles 4d

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LV433707 key specifications
ParameterValue
Control typeToggle
Display typeLCD display
Network typeAC
Protection typeL : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection G : for ground fault protection
Range of productComPact NSX400...630
Type of measurementEnergy meter
Product or component typeCircuit breaker
Long-time protection delay adjustment type trAdjustable
Short-time protection delay adjustment type tsdAdjustable 5 settings
Short-time protection pick-up adjustment type isdAdjustable
Ground-fault protection pick-up adjustment type igAdjustable 9 settings
Instantaneous protection pick-up adjustment type iiAdjustable

All specifications

LV433707 additional specifications
ParameterValue
Ground-fault protection time delay adjustment type tgAdjustable
Long-time pick-up adjustment type ir (thermal protection)Adjustable 9 settings
Voltage800 V AC 50/60 Hz
[Ue] rated operational voltage690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
Line rated current630 A 104 °F (40 °C)
[Ics] rated service short-circuit breaking capacity200 kA 220/240 V AC 50/60 Hz IEC 60947-2 200 kA 380/415 V AC 50/60 Hz IEC 60947-2 200 kA 440 V AC 50/60 Hz IEC 60947-2 80 kA 500 V AC 50/60 Hz IEC 60947-2 16 kA 525 V AC 50/60 Hz IEC 60947-2 12 kA 660/690 V AC 50/60 Hz IEC 60947-2
[Icu] rated ultimate short-circuit breaking capacity200 kA Icu 220/240 V AC 50/60 Hz IEC 60947-2 200 kA Icu 380/415 V AC 50/60 Hz IEC 60947-2 200 kA Icu 440 V AC 50/60 Hz IEC 60947-2 80 kA Icu 500 V AC 50/60 Hz IEC 60947-2 65 kA Icu 525 V AC 50/60 Hz IEC 60947-2 45 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2
Network frequency50/60 Hz
Poles4P
Protected poles description4t 3t + N/2 3t 3t + OSN
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to IEC 62262
IP degree of protectionIP40 conforming to IEC 60529
Communication of dataDemand current and power Maintenance indicators Energy metering Time-stamped histories and event tables Power quality Protection and alarm settings Maximeters/minimeters Instantaneous and demand values
Mounting supportBackplate
Circuit breaker mounting modeFixed
Connection pitch1.8 in (45 mm)
Upside connectionFront
Downside connectionFront
Pollution degree3 IEC 60664-1
Relative humidity0...95 %
Operating altitude0...6561.68 ft (0...2000 m) without derating 2000 m...5000 m with derating
Electrical shock protection classClass II
Depth4.3 in (110 mm)
Width7.3 in (185 mm)
Height10.04 in (255 mm)
Electrical durability2000 cycles 690 V In 6000 cycles 690 V In/2 4000 cycles 440 V In 8000 cycles 440 V In/2
Mechanical durability15000 cycles
StandardsEN/IEC 60947
RangeComPact
CategoryUS10DE201101
Thermal memory20 minutes before and after tripping
Trip unit nameMicroLogic 6.3 E
Local signallingFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
Neutral positionLeft
Trip unit rating630 A 104 °F (40 °C)
Device short nameNSX630R
Safety categoryR 200 kA 415 V AC
Device applicationDistribution
Overvoltage categoryClass II
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes EN/IEC 60947-2
Neutral protection settings0.5 x Ir 3t + N/2) 1 x Ir 4t) 1.6 x Ir 3t + OSN) No protection 3t)
Trip unit protection functionsLSIG
Zone selective interlocking ZSIWith
Ambient air temperature for storage-40...185 °F (-40...85 °C)
Ambient air temperature for operation-13...158 °F (-25...70 °C)
Number of slots for electrical auxiliaries6
[Tr] Long-Time protection delay adjustment range15...400 s 1.5 x Ir 0.35...11 s 7.2 x Ir 0.5...16 s 6 x Ir
[Ir] long-time protection pick-up adjustment range250...630 A
[tsd] short-time protection delay adjustment range0...0.4 s
[Isd] short-time protection pick-up adjustment range1.5...11 x In
[Ig] ground-fault protection pick-up adjustment range0.4...1 x In In = 40 A 0.2...1 x In In > 40 A Ig enable on/off
[Ii] instantaneous protection pick-up adjustment range1.5...11 x In
[Tg] Ground-Fault protection time delay adjustment range0...0.4 s I²t=off 0.1...0.4 s I²t=on
MPN