Skip to main content
Schneider Electric LV433941

Schneider Electric LV433941

MPNLV433941
Obsolete

LV433941 - CIRCUIT BREAKER by SCHNEIDER ELECTRIC

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LV433941 key specifications
ParameterValue
Control typeToggle
Network typeAC
Protection typeL : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection R : for earth-leakage protection
Range of productComPact NSX400...630
Product or component typeEarth leakage circuit breaker
Long-time protection delay adjustment type trFixed
Short-time protection delay adjustment type tsdFixed
Short-time protection pick-up adjustment type isdAdjustable
Instantaneous protection pick-up adjustment type iiFixed
Earth-leakage protection sensitity adjustment type iδnAdjustable
Earth-leakage protection time delay adjustement type δtAdjustable
Long-time pick-up adjustment type ir (thermal protection)Adjustable 9 settings

All specifications

LV433941 additional specifications
ParameterValue
Voltage500 V AC 50/60 Hz
[Ue] rated operational voltage440 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
Current570 A at 40 °C
[Ics] rated service short-circuit breaking capacity85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 42 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
[Icu] rated ultimate short-circuit breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
Network frequency50/60 Hz
Poles4P
Protected poles description4t 3t 3t + N/2
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to IEC 62262
IP degree of protectionIP40 conforming to IEC 60529
Mounting supportBackplate
Circuit breaker mounting modeFixed
Connection pitch45 mm
Upside connectionFront
Downside connectionFront
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
Electrical shock protection classClass II
Depth86 mm
Width140 mm
Height161 mm
Electrical durability4000 cycles at 440 V In 8000 cycles at 440 V In/2
Mechanical durability15000 cycles
StandardsEN/IEC 60947
RangeComPact
Thermal memory20 minutes before and after tripping
Trip unit nameMicroLogic 4.3
Local signallingFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
Neutral positionLeft
Trip unit rating570 A at 40 °C
Device short nameVigiCompact NSX630N
Safety categoryN 50 kA 415 V AC
Device applicationDistribution
Overvoltage categoryClass II
Trip unit technologyElectronic
Earth-leakage protectionIntegrated
Suitability for isolationYes conforming to EN/IEC 60947-2
Neutral protection settings0.5 x Ir (3t + N/2) 1 x Ir (4t) No protection (3t)
Earth-leakage protection classClass A
Trip unit protection functionsLSoIR
Zone selective interlocking ZSIWithout
Ambient air temperature for storage-40...85 °C
Ambient air temperature for operation-25...70 °C
Earth-leakage protection specific modeOFF using the IΔn rotary switch
Number of slots for electrical auxiliaries6 slot(s)
[Tr] Long-Time protection delay adjustment range11 s at 7.2 x Ir 16 s at 6 x Ir 400 s at 1.5 x Ir
[Ir] long-time protection pick-up adjustment range250...570 A
[tsd] short-time protection delay adjustment range0.02 s
[Isd] short-time protection pick-up adjustment range1.5...10 x Ir
[Ii] instantaneous protection pick-up adjustment range6900 A
[δt] earth-leakage protection time delay adjustment range0 ms 60 ms 150 ms 500 ms 1 s
[IΔn] earth-leakage protection sensitivity adjustment range300 mA 500 mA 1 A 3 A 5 A 10 A
MPN
LV433941