Schneider Electric LV438245

Schneider LV438245 TM250DC trip unit, 250 A, 3-pole, DC

MPNLV438245
Obsolete

Schneider Electric ComPact NSX250 DC LV438245 trip unit, TM-D, thermal-magnetic, 250 A, 3-pole, 750 V DC, IEC 60947-2, LI protection, adjustable Isd, fixed Tr/Tsd, discontinued.

$172.48 – $220.51Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LV438245 key specifications
ParameterValue
Network typeDC
Protection typeL : for overload protection (thermal) I : for short-circuit protection (magnetic)
Range of productComPact NSX100...250 DC
Product or component typeTrip unit
Long-time protection delay adjustment type trFixed
Short-time protection delay adjustment type tsdFixed
Short-time protection pick-up adjustment type isdAdjustable
Long-time pick-up adjustment type ir (thermal protection)Adjustable
[Ue] rated operational voltage750 V DC
Trip unit rated current250 A at 40 °C
Poles3P
Protected poles description3t

All specifications

LV438245 additional specifications
ParameterValue
StandardsIEC 60947-2
RangeComPact
Trip unit nameTM-D
Device applicationDistribution
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Trip unit protection functionsLI
Ambient air temperature for storage-50...85 °C
Ambient air temperature for operation-25...70 °C
[Ir] long-time protection pick-up adjustment range0.7...1 x In
[Isd] short-time protection pick-up adjustment range5...10 x In

Product details

Overview

The LV438245 is a Schneider ComPact NSX250 DC thermal-magnetic trip unit rated 250 A at 750 V DC, with LI protection (thermal overload and magnetic short-circuit) and an adjustable short-time pickup Isd. It is a 3-pole unit for DC distribution, fixed long-time and short-time delays, and carries certifications including ASTA, KEMA, LCIE, and ASEFA.

Schneider discontinued the LV438245 on 2023-06-15; it is no longer in active production and must be sourced through surplus or broker channels.

Compared to the LV438246, the LV438245 switches 250 A versus 200 A, both at 750 V DC with 3 poles and the same TM-D trip unit; choose the LV438245 when the load requires the higher 250 A rating.

MPN
LV438245