LV438279 key specifications
ParameterValue
Control typeToggle
Network typeDC
Protection typeL : for overload protection (thermal) I : for short-circuit protection (magnetic)
Range of productComPact NSX400...630 DC
Product or component typeCircuit breaker
Long-time pick-up adjustment type ir (thermal protection)Adjustable
Voltage750 V DC conforming to IEC 60947-2
[Ue] rated operational voltage750 V DC
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947-2
Current600 A at 40 °C
[Ics] rated service short-circuit breaking capacity100 kA at 750 V DC conforming to IEC 60947-2
[Icu] rated ultimate short-circuit breaking capacity100 kA Icu at 250 V DC 1P conforming to IEC 60947-2 100 kA Icu at 500 V DC 2P conforming to IEC 60947-2 100 kA Icu at 750 V DC 3P conforming to IEC 60947-2

All specifications

LV438279 additional specifications
ParameterValue
Poles3P
Protected poles description3t
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to IEC 62262
IP degree of protectionIP40 conforming to IEC 60529
Mounting supportBackplate
Circuit breaker mounting modeFixed
Connection pitch45 mm
Upside connectionFront
Downside connectionFront
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
Electrical shock protection classClass II
Depth110 mm
Width140 mm
Height255 mm
Electrical durability1000 cycles at 750 V In 2000 cycles at 750 V In/2
Mechanical durability5000 cycles
StandardsEN/IEC 60947
RangeComPact
Trip unit nameTM-DC
Trip unit rating600 A at 40 °C
Device short nameNSX630S DC
Safety categoryS 100 kA 500 V DC
Device applicationDistribution
Overvoltage categoryClass II
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Ambient air temperature for storage-50...85 °C
Ambient air temperature for operation-25...70 °C
Number of slots for electrical auxiliaries6 slot(s)
[Ir] long-time protection pick-up adjustment range0.7...1 x In