Skip to main content
Schneider Electric LV438606

Schneider Electric LV438606

MPNLV438606
Obsolete

LV438606 by SQUARE D

$143.51Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LV438606 key specifications
ParameterValue
Control typeToggle
Network typeDC AC
Protection typefor overload protection (thermal) for short-circuit protection (magnetic)
Range of productComPact NSX100...250 DC ComPact NSX100...250
Product or component typeCircuit breaker
Long-time pick-up adjustment type ir (thermal protection)Fixed
Voltage750 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz 500 V DC
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947-2
Current40 A at 40 °C
[Ics] rated service short-circuit breaking capacity5 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 250 V DC conforming to IEC 60947-2 36 kA at 125 V DC conforming to IEC 60947-2 36 kA at 500 V DC conforming to IEC 60947-2 10 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
[Icu] rated ultimate short-circuit breaking capacity8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 250 V DC 1 pole conforming to IEC 60947-2 85 kA Icu at 500 V DC 2 poles in series conforming to IEC 60947-2

All specifications

LV438606 additional specifications
ParameterValue
Network frequency50/60 Hz
Poles2P
Protected poles description2t
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to IEC 62262
IP degree of protectionIP40 conforming to IEC 60529
Mounting supportBackplate
Circuit breaker mounting modeFixed
Connection pitch35 mm
Upside connectionFront
Downside connectionFront
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
Electrical shock protection classClass II
Depth86 mm
Width70 mm
Height161 mm
Electrical durability10000 cycles at 277 V In 20000 cycles at 277 V In/2
Mechanical durability20000 cycles
StandardsEN/IEC 60947
RangeComPact
Trip unit nameTM-D
Trip unit rating40 A at 40 °C
Device short nameNSX100M
Safety categoryM 25 kA 415 V AC
Device applicationDistribution
Overvoltage categoryClass II
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Ambient air temperature for storage-50...85 °C
Ambient air temperature for operation-25...70 °C
[Im] magnetic protection pick-up range500 A
[Ir] long-time protection pick-up adjustment range1 In
MPN
LV438606