Skip to main content
Schneider Electric LV480500

Schneider Electric LV480500

MPNLV480500
Obsolete

Switch disconnector fuse, FuPact INFD200, 200 A, 3 poles 3F, fuse type DIN 0, front control

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LV480500 key specifications
ParameterValue
Fuse typeDIN
Control typeOperating shaft (without handle)
Network typeAC DC
Range of productINF200...800
Product or component typeSwitch-disconnector-fuse
Voltage1000 V AC 50/60 Hz 1000 V DC
[Ue] rated operational voltage690 V AC 50/60 Hz 1000 V AC 50/60 Hz AC-20 1000 V DC DC-20 750 V DC
[Uimp] rated impulse withstand voltage12 kV
[Icw] rated short-time withstand current8 kA for 1 s 1.46 kA for 30 s 1.79 kA for 20 s 4.62 kA for 3 s
[Ie] rated operational currentAC-22A: 200 A at 220/240 V AC 50/60 Hz AC-22A: 200 A at 380/415 V AC 50/60 Hz AC-22A: 200 A at 440/480 V AC 50/60 Hz AC-22A: 200 A at 480 V AC 50/60 Hz conforming to NEMA AC-22A: 200 A at 500/525 V AC 50/60 Hz AC-22A: 200 A at 660/690 V AC 50/60 Hz AC-23A: 200 A at 220/240 V AC 50/60 Hz AC-23A: 200 A at 380/415 V AC 50/60 Hz AC-23A: 200 A at 440/480 V AC 50/60 Hz AC-23A: 200 A at 480 V AC 50/60 Hz conforming to NEMA AC-23A: 200 A at 500/525 V AC 50/60 Hz AC-23A: 200 A at 660/690 V AC 50/60 Hz DC-22A: 200 A at 125 V DC (1 pole) DC-22A: 200 A at 250 V DC (2 poles in series) DC-22A: 200 A at 500 V DC (3 poles in series) DC-23A: 200 A at 125 V DC (1 pole) DC-23A: 200 A at 250 V DC (2 poles in series) DC-23A: 200 A at 500 V DC (3 poles in series)
[Im] rated making and breaking capacityIcm 220 kA at 500 V conforming to DIN (with fuse) Icn 100 kA at 500 V conforming to DIN (with fuse) Icm 176 kA at 415 V conforming to DIN (with fuse) Icm 176 kA at 690 V conforming to DIN (with fuse) Icm 28 kA at 690 V (without fuse) Icm 35 kA at 415 V (without fuse) Icn 80 kA at 415 V conforming to DIN (with fuse) Icn 80 kA at 690 V conforming to DIN (with fuse) Icm 37.5 kA at 500 V (without fuse)
[Ith] conventional free air thermal current200 A ( 40 °C ) power dissipation per fuse: 17 W vertical 141 A ( 70 °C ) horizontal 141 A ( 70 °C ) vertical 151 A ( 65 °C ) horizontal 151 A ( 65 °C ) vertical 160 A ( 60 °C ) horizontal 160 A ( 60 °C ) vertical 169 A ( 55 °C ) horizontal 169 A ( 55 °C ) vertical 177 A ( 50 °C ) horizontal 177 A ( 50 °C ) vertical 185 A ( 45 °C ) horizontal 185 A ( 45 °C ) vertical 193 A ( 40 °C ) horizontal 200 A ( 35 °C ) horizontal

All specifications

LV480500 additional specifications
ParameterValue
[Ithe] conventional enclosed thermal current180 A at 40 °C, Power dissipation per fuse: 18 W (600 mm x 350 mm x 300 mm) 200 A at 40 °C, Power dissipation per fuse: 15 W (600 mm x 350 mm x 300 mm)
Maximum powerAC-23: 110 kW at 380/400 V AC 50/60 Hz AC-23: 110 kW at 415 V AC 50/60 Hz AC-23: 132 kW at 500/525 V AC 50/60 Hz AC-23: 200 kW at 660/690 V AC 50/60 Hz AC-23: 60 kW at 220/240 V AC 50/60 Hz
Network frequency50/60 Hz
Poles description3P
Protected poles description3f
Rated dutyUninterrupted
IP degree of protectionIP20 fuse compartment:
Mounting modeFixed
Mounting supportMounting plate
Rotary handle mounting locationFront
Connections terminalsScrew connection
Connections - terminalsScrew connection M8 200 A
Pollution degree3
Depth149 mm
Width175.5 mm
Height199 mm
Electrical durabilityAC-22A: 1000 cycles 500 V AC 50/60 Hz AC-22A: 1000 cycles 690 V AC 50/60 Hz AC-23A: 1000 cycles 500 V AC 50/60 Hz AC-23A: 1000 cycles 690 V AC 50/60 Hz
Mechanical durability10000 cycles
StandardsEN/IEC 60947-1 EN/IEC 60947-3
RangeFuPact
DesignHorizontal design
Fuse sizeNH0
Contact operationDouble-break
Device short nameINFD200
Tightening torque15...22 N.m for terminal
Device applicationProtection
Suitability for isolationYes conforming to IEC 60947-1
Contact position indicatorYes
MPN
LV480500