
Schneider Electric LV480510
MPNLV480510
Obsolete
Switch disconnector fuse, FuPact INFD630, 630 A, 4 poles 3F, fuse type DIN 3, front control
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Fuse type | DIN |
| Control type | Operating shaft (without handle) |
| Network type | AC DC |
| Range of product | INF200...800 |
| Product or component type | Switch-disconnector-fuse |
| Voltage | 1000 V AC 50/60 Hz 1000 V DC |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz 1000 V AC 50/60 Hz AC-20 1000 V DC DC-20 750 V DC |
| [Uimp] rated impulse withstand voltage | 12 kV |
| [Icw] rated short-time withstand current | 20 kA for 1 s 4 kA for 30 s 5 kA for 20 s 11.6 kA for 3 s |
| [Ie] rated operational current | AC-22A: 630 A at 220/240 V AC 50/60 Hz AC-22A: 630 A at 380/415 V AC 50/60 Hz AC-22A: 630 A at 440/480 V AC 50/60 Hz AC-22A: 630 A at 500/525 V AC 50/60 Hz AC-22A: 630 A at 660/690 V AC 50/60 Hz AC-23A: 630 A at 220/240 V AC 50/60 Hz AC-23A: 630 A at 380/415 V AC 50/60 Hz AC-23A: 630 A at 440/480 V AC 50/60 Hz AC-23A: 630 A at 500/525 V AC 50/60 Hz AC-23A: 630 A at 660/690 V AC 50/60 Hz DC-22A: 630 A at 250 V DC (2 poles in series) DC-22A: 630 A at 500 V DC (3 poles in series) DC-23A: 630 A at 250 V DC (2 poles in series) DC-23A: 630 A at 500 V DC (3 poles in series) AC-22A: 630 A at 480 V AC 50/60 Hz conforming to NEMA AC-23A: 630 A at 480 V AC 50/60 Hz conforming to NEMA DC-22A: 630 A at 125 V DC (1 pole) DC-23A: 630 A at 125 V DC (1 pole) |
| [Im] rated making and breaking capacity | Icm 220 kA at 500 V conforming to DIN (with fuse) Icn 100 kA at 500 V conforming to DIN (with fuse) Icm 176 kA at 415 V conforming to DIN (with fuse) Icm 176 kA at 690 V conforming to DIN (with fuse) Icn 80 kA at 415 V conforming to DIN (with fuse) Icn 80 kA at 690 V conforming to DIN (with fuse) Icm 55 kA at 690 V (without fuse) Icm 77 kA at 415 V (without fuse) Icm 83 kA at 500 V (without fuse) |
| [Ith] conventional free air thermal current | 630 A ( 40 °C ) power dissipation per fuse: 60 W vertical 403 A ( 70 °C ) horizontal 431 A ( 65 °C ) horizontal 446 A ( 70 °C ) vertical 457 A ( 60 °C ) horizontal 476 A ( 65 °C ) vertical 482 A ( 55 °C ) horizontal 505 A ( 50 °C ) horizontal 505 A ( 60 °C ) vertical 528 A ( 45 °C ) horizontal 532 A ( 55 °C ) vertical 549 A ( 40 °C ) horizontal 558 A ( 50 °C ) vertical 570 A ( 35 °C ) horizontal 583 A ( 45 °C ) vertical |
All specifications
| Parameter | Value |
|---|---|
| [Ithe] conventional enclosed thermal current | 570 A at 40 °C, Power dissipation per fuse: 50 W (800 mm x 1000 mm x 330 mm) 630 A at 40 °C, Power dissipation per fuse: 60 W |
| Maximum power | AC-23: 200 kW at 220/240 V AC 50/60 Hz AC-23: 355 kW at 380/400 V AC 50/60 Hz AC-23: 355 kW at 415 V AC 50/60 Hz AC-23: 450 kW at 500/525 V AC 50/60 Hz AC-23: 630 kW at 660/690 V AC 50/60 Hz |
| Network frequency | 50/60 Hz |
| Poles description | 4P |
| Protected poles description | 3f |
| Rated duty | Uninterrupted |
| IP degree of protection | IP20 fuse compartment: |
| Mounting mode | Fixed |
| Mounting support | Mounting plate |
| Rotary handle mounting location | Front |
| Connections terminals | Screw connection |
| Connections - terminals | Screw connection M12 630 A |
| Pollution degree | 3 |
| Depth | 233 mm |
| Width | 429 mm |
| Height | 306 mm |
| Electrical durability | AC-22A: 1000 cycles 500 V AC 50/60 Hz AC-22A: 1000 cycles 690 V AC 50/60 Hz AC-23A: 1000 cycles 500 V AC 50/60 Hz AC-23A: 1000 cycles 690 V AC 50/60 Hz |
| Mechanical durability | 5000 cycles |
| Standards | EN/IEC 60947-1 EN/IEC 60947-3 |
| Range | FuPact |
| Design | Horizontal design |
| Fuse size | NH3 |
| Contact operation | Double-break |
| Device short name | INFD630 |
| Tightening torque | 50...75 N.m for terminal |
| Device application | Protection |
| Suitability for isolation | Yes conforming to IEC 60947-1 |
| Contact position indicator | Yes |
MPN
LV480510