Skip to main content
Schneider Electric LV480656

Schneider Electric LV480656

MPNLV480656
Obsolete

Switch disconnector fuse. FuPact INFC32. 32 A. 3 poles 3F. fuse type NFC 14 x 51 mm. front control

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LV480656 key specifications
ParameterValue
Fuse typeNFC
Control typeWithout handle
Network typeDC AC
Range of productINF32
Product or component typeSwitch-disconnector-fuse
Voltage1000 V AC 50/60 Hz 1000 V DC
[Ue] rated operational voltage250 V DC 690 V AC 50/60 Hz 690 V AC 50/60 Hz AC-20 690 V DC DC-20
[Uimp] rated impulse withstand voltage12 kV
[Icw] rated short-time withstand current1 kA for 1 s 0.18 kA for 30 s 0.22 kA for 20 s 0.57 kA for 3 s
[Ie] rated operational currentAC-22A: 32 A at 220/240 V AC 50/60 Hz AC-22A: 32 A at 380/415 V AC 50/60 Hz AC-22A: 32 A at 440/480 V AC 50/60 Hz AC-22A: 32 A at 500/525 V AC 50/60 Hz AC-22A: 32 A at 660/690 V AC 50/60 Hz AC-23A: 32 A at 220/240 V AC 50/60 Hz AC-23A: 32 A at 380/415 V AC 50/60 Hz AC-23A: 32 A at 440/480 V AC 50/60 Hz AC-23A: 32 A at 500/525 V AC 50/60 Hz AC-23A: 32 A at 660/690 V AC 50/60 Hz DC-22A: 32 A at 125 V DC (2 poles in series) DC-22A: 32 A at 250 V DC (2 poles in series) DC-23A: 32 A at 500 V DC (4 poles in series) DC-23A: 32 A at 750 V DC (4 poles in series)
[Im] rated making and breaking capacityIcm 105 kA at 690 V conforming to DIN (with fuse) Icm 176 kA at 415 V conforming to BS (with fuse) Icm 220 kA at 500 V conforming to DIN (with fuse) Icn 100 kA at 500 V conforming to DIN (with fuse) Icn 50 kA at 690 V conforming to DIN (with fuse) Icn 80 kA at 415 V conforming to BS (with fuse) Icm 6 kA at 690 V (without fuse) Icm 9 kA at 415 V (without fuse) Icm 7.5 kA at 500 V (without fuse)
[Ith] conventional free air thermal current20.5 A ( 70 °C ) horizontal 22 A ( 65 °C ) horizontal 23.5 A ( 60 °C ) horizontal 24.4 A ( 70 °C ) vertical 25 A ( 55 °C ) horizontal 25 A ( 65 °C ) vertical 25.6 A ( 60 °C ) vertical 26.5 A ( 50 °C ) horizontal 27.2 A ( 55 °C ) vertical 28 A ( 45 °C ) horizontal 28.8 A ( 50 °C ) vertical 29.5 A ( 40 °C ) horizontal 30.4 A ( 45 °C ) vertical 31 A ( 35 °C ) horizontal 32 A ( 40 °C ) power dissipation per fuse: 3.5 W 32 A ( 40 °C ) vertical

All specifications

LV480656 additional specifications
ParameterValue
[Ithe] conventional enclosed thermal current32 A at 40 °C, Power dissipation per fuse: 3.5 W (300 mm x 350 mm x 200 mm)
Maximum power14 kW at 380/400 V AC 50/60 Hz 15 kW at 415 V AC 50/60 Hz 18 kW at 500/525 V AC 50/60 Hz 25 kW at 660/690 V AC 50/60 Hz 8 kW at 220/240 V AC 50/60 Hz
Network frequency50/60 Hz
Poles description3P
Protected poles description3f
Rated dutyUninterrupted
Intermittent duty classClass 120 - 60 %
IK degree of protectionIK07 conforming to EN 50102 IK10 conforming to EN 50102
IP degree of protectionIP20 conforming to IEC 60529 IP65 conforming to IEC 60529
Mounting supportMounting plate DIN rail
Rotary handle mounting styleExtended Direct
Rotary handle mounting locationFront
Connections terminalsScrew clamp terminals
Connections - terminalsScrew clamp terminals 32 A 0.5...10 mm² flexible Screw clamp terminals 32 A 0.5...10 mm² rigid
Pollution degree3
Depth105 mm
Width106 mm
Height97 mm
Electrical durabilityAC-22A: 1500 cycles 500 V AC 50/60 Hz AC-22A: 1500 cycles 690 V AC 50/60 Hz AC-23A: 1500 cycles 500 V AC 50/60 Hz AC-23A: 1500 cycles 690 V AC 50/60 Hz
Mechanical durability10000 cycles
StandardsEN/IEC 60269-4 EN/IEC 60947-3 EN/IEC 60947-5 EN/IEC 60269-1 EN/IEC 60947-1
RangeFuPact
DesignHorizontal design
Fuse size14 x 51 mm
Contact operationDouble-break
Device short nameINFC32
Tightening torque2 N.m for terminal
Device applicationProtection
Suitability for isolationYes
Contact position indicatorYes
Ambient air temperature for storage-50...85 °C
Ambient air temperature for operation-25...70 °C
MPN
LV480656