Skip to main content
Schneider Electric LV480751

Schneider Electric LV480751

MPNLV480751
Active

Fuse switch disconnector, FuPacT ISFT100N, 100A, DIN NH000, 3 poles, 60mm busbars mounting, upstream distribution

$140.79 – $326.71Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LV480751 key specifications
ParameterValue
Fuse typeDIN
Control typeFuse carriers handle
Product or component typeFuse-switch disconnector
Voltage1000 V AC 50/60 Hz 1000 V DC
[Ue] rated operational voltage690 V AC 50/60 Hz 440 V DC 800 V AC 50/60 Hz AC-20 800 V DC DC-20
[Uimp] rated impulse withstand voltage6 kV
[Icw] rated short-time withstand current3.6 kA for 1 s
[Ie] rated operational currentAC-21B: 100 A at 220/240 V AC 50/60 Hz AC-21B: 100 A at 380/415 V AC 50/60 Hz AC-21B: 100 A at 440/480 V AC 50/60 Hz AC-21B: 100 A at 500 V AC 50/60 Hz AC-21B: 100 A at 660/690 V AC 50/60 Hz AC-22B: 100 A at 220/240 V AC 50/60 Hz AC-22B: 100 A at 380/415 V AC 50/60 Hz AC-22B: 100 A at 440/480 V AC 50/60 Hz AC-22B: 100 A at 500 V AC 50/60 Hz DC-21B: 100 A at 220 V DC (3 poles in series) DC-21B: 100 A at 440 V DC (3 poles in series) DC-22B: 100 A at 220 V DC (3 poles in series) DC-22B: 100 A at 440 V DC (3 poles in series)
[Icm] rated short-circuit making capacity5.2 kA at 690 V
[Iq] breaking capacity with fuses (kA RMS)80 kA at 415 V (AC) 80 kA at 500 V (AC) 25 kA at 690 V (AC)
[Ith] conventional free air thermal current100 A ( 40 °C ) power dissipation per fuse: 9 W
[Ithe] conventional enclosed thermal current100 A at 40 °C, Power dissipation per fuse: 9 W

All specifications

LV480751 additional specifications
ParameterValue
Maximum power dissipation per pole11 W
Poles description3P
Rated dutyUninterrupted
IK degree of protectionIK07 conforming to EN 50102
IP degree of protectionIP3x front face: conforming to IEC 60529
Mounting supportBackplate Busbars DIN rail with accessory
Mounting locationSide by side
Mounting positionVertical Horizontal
Cable entryTop
Connections - terminalsCable connectors upstream 2.5...50 mm²
Pollution degree3 conforming to IEC 60947
Electrical shock protection classClass II front face
Depth80 mm
Width53 mm
Height216 mm
Electrical durabilityAC-21B: 300 cycles 690 V AC 50/60 Hz AC-22B: 300 cycles 500 V AC 50/60 Hz AC-23B: 300 cycles 415 V AC 50/60 Hz
Mechanical durability2000 cycles
StandardsEN/IEC 60947-1 EN/IEC 60947-3
RangeFuPacT
Fuse sizeNH000
Visible breakYes
Contact operationSingle-break
Device short nameISFT100N
Tightening torque4.5 N.m for terminal
Device applicationDistribution Equipment protection, monitoring and control
Number of fuse carriers3
Provision for padlockingLead seal
Suitability for isolationYes conforming to EN/IEC 60947-3
Contact position indicatorYes
Ambient air temperature for storage-50...85 °C
Ambient air temperature for operation-20...70 °C
MPN