Skip to main content
Schneider Electric LV480801

Schneider Electric LV480801

MPNLV480801
Obsolete

Fuse switch disconnector, FuPacT ISFT160, 160A, DIN NH00, 3 poles, backplate mounting, M8 terminals

$68.49Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LV480801 key specifications
ParameterValue
Fuse typeDIN
Control typeFuse carriers handle
Product or component typeFuse-switch disconnector
Voltage1000 V AC 50/60 Hz 1000 V DC
[Ue] rated operational voltage690 V AC 50/60 Hz 440 V DC 800 V AC 50/60 Hz AC-20 800 V DC DC-20
[Uimp] rated impulse withstand voltage8 kV
[Icw] rated short-time withstand current5 kA for 1 s
[Ie] rated operational currentAC-21B: 160 A at 220/240 V AC 50/60 Hz AC-21B: 160 A at 380/415 V AC 50/60 Hz AC-21B: 160 A at 440/480 V AC 50/60 Hz AC-21B: 160 A at 500 V AC 50/60 Hz AC-21B: 160 A at 660/690 V AC 50/60 Hz AC-22B: 160 A at 220/240 V AC 50/60 Hz AC-22B: 160 A at 380/415 V AC 50/60 Hz AC-22B: 160 A at 440/480 V AC 50/60 Hz AC-22B: 160 A at 500 V AC 50/60 Hz DC-21B: 160 A at 220 V DC (3 poles in series) DC-21B: 125 A at 440 V DC (3 poles in series) DC-22B: 160 A at 220 V DC (3 poles in series)
[Icm] rated short-circuit making capacity7.65 kA at 690 V
[Iq] breaking capacity with fuses (kA RMS)80 kA at 415 V (AC) 80 kA at 500 V (AC) 25 kA at 690 V (AC)
[Ith] conventional free air thermal current160 A ( 40 °C ) power dissipation per fuse: 12 W
[Ithe] conventional enclosed thermal current160 A at 40 °C, Power dissipation per fuse: 12 W

All specifications

LV480801 additional specifications
ParameterValue
Maximum power dissipation per pole15 W
Poles description3P
Rated dutyUninterrupted
IK degree of protectionIK07 conforming to EN 50102
IP degree of protectionIP3x front face: conforming to IEC 60529
Mounting modeFixed
Mounting supportBackplate
Mounting locationSide by side
Mounting positionVertical Horizontal
Connections - terminalsM8 terminals
Pollution degree3 conforming to IEC 60947
Electrical shock protection classClass II front face
Depth80 mm
Width106 mm
Height206 mm
Electrical durabilityAC-21B: 200 cycles 690 V AC 50/60 Hz AC-22B: 200 cycles 500 V AC 50/60 Hz AC-23B: 200 cycles 415 V AC 50/60 Hz
Mechanical durability1600 cycles
StandardsEN/IEC 60947-1 EN/IEC 60947-3
RangeFuPacT
Fuse sizeNH00
Visible breakYes
Contact operationSingle-break
Device short nameISFT160
Tightening torque5 N.m for terminal
Device applicationEquipment protection, monitoring and control Distribution
Signalling functionSeparated fuse monitor
Number of fuse carriers3
Provision for padlockingLead seal
Suitability for isolationYes conforming to EN/IEC 60947-3
Contact position indicatorYes
Ambient air temperature for storage-50...85 °C
Ambient air temperature for operation-20...70 °C
MPN
LV480801