Skip to main content
Schneider Electric LV525351

Schneider Electric LV525351

MPNLV525351
Obsolete

circuit breaker EasyPact CVS250F, 36 kA at 415 VAC, 4P 4d, 160 A rating thermal magnetic TM-D trip unit

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LV525351 key specifications
ParameterValue
Control typeToggle
Network typeAC
Protection typeOverload protection (thermal) Short-circuit protection (magnetic)
Range of productEasyPact CVS100...250
Product or component typeCircuit breaker
Long time delay adjustment typeFixed
Long time pick-up adjustment type irAdjustable
Instantaneous pick-up adjustment type iiFixed
[Uimp] rated impulse withstand voltage8 kV conforming to EN/IEC 60947-2
Current160 A at 40 °C
Breaking capacity codeF
[Icu] breaking capacity36 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2

All specifications

LV525351 additional specifications
ParameterValue
[Ics] rated service breaking capacity18 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description4P
Protected poles description4D
Utilisation categoryCategory A
IP degree of protectionIP40
Mounting modeFixed
Mounting supportBackplate
Connection pitch35 mm
Upside connectionFront
Downside connectionFront
Connections - terminalsScrew connection
Pollution degree3 conforming to IEC 60664-1
Electrical shock protection classClass II
Depth86 mm
Width140 mm
Height161 mm
Product weight2.6 kg
Electrical durability10000 cycles 415 V In conforming to IEC 60947-2
Mechanical durability20000 cycles
StandardsIEC 60947-2 EN 60947-2
RangeEasyPact
Trip unit nameTM-D
Neutral positionLeft
Trip unit rating160 A at 40 °C
Device short nameCVS250F
Compatibility codeCVS250
Device applicationDistribution
Trip unit technologyThermal-magnetic
Contact position indicatorYes
Neutral protection setting1 x Ir (4D)
Long time pick-up adjustment range0.7...1 x In
Ambient air temperature for storage-50...85 °C
Thermal protection adjustment range112...160 A
Ambient air temperature for operation-25...70 °C
Earth leakage protection (Vigi add on)Without
Instantaneous pick-up adjustment range1250 A
MPN
LV525351