Specifications

LV848106 key specifications
ParameterValue
Control typePush-button
Performance typeH1 100 kA 415 V AC
Product or component typeCircuit breaker
Voltage1000 V AC 50/60 Hz
[Ue] rated operational voltage690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage12 kV
[Icw] rated short-time withstand current100 kA 0.5 s 100 kA 1 s 100 kA 3 s
Line rated current4000 A 104 °F (40 °C)
[Ics] rated service breaking capacity100 kA 220/415 V AC 50/60 Hz 100 kA 440 V AC 50/60 Hz 100 kA 500/525 V AC 50/60 Hz 100 kA 660/690 V AC 50/60 Hz
[Icm] rated short-circuit making capacity220 kA 220/415 V AC 50/60 Hz 220 kA 440 V AC 50/60 Hz 220 kA 500/525 V AC 50/60 Hz 220 kA 660/690 V AC 50/60 Hz
[Icu] rated ultimate short-circuit breaking capacity100 kA 220/415 V AC 50/60 Hz 100 kA 440 V AC 50/60 Hz 100 kA 500/525 V AC 50/60 Hz 100 kA 660/690 V AC 50/60 Hz
Power dissipation in260 W

All specifications

LV848106 additional specifications
ParameterValue
Poles description3P
IP degree of protectionIP30 conforming to EN 60529
Mounting modeFixed
Mounting supportRails Base plate
Connection pitch9.06 in (230 mm)
Upside connectionRear
Downside connectionRear
Maximum closing response time80 ms
Pollution degree3 IEC 60947-1
Operating altitude0...6561.68 ft (0...2000 m) without derating 2000...5000 m with derating
Depth11.8 in (300 mm)
Width30.2 in (767 mm)
Height13.9 in (352 mm)
Electrical durabilityAC-3 6000 cycles 440/690 V AC 50/60 Hz EN/IEC 60947-3 1500 cycles 440 V AC 50/60 Hz EN/IEC 60947-2 1500 cycles 690 V AC 50/60 Hz EN/IEC 60947-2 AC-23A 1500 cycles 440 V AC 50/60 Hz EN/IEC 60947-3 AC-23A 1500 cycles 690 V AC 50/60 Hz EN/IEC 60947-3
Mechanical durability10000 cycles with periodic preventive maintenance
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H IEC 61557-12
RangeMasterPacT
Control unitWithout control unit
Sensor rating2000 A 2500 A 3200 A 4000 A
Device short nameMTZ3 40 H1
Device applicationPower distribution protection
Selectivity categoryCategory B
Maximum breaking time25 ms
Suitability for isolationYes EN/IEC 60947-2
Ambient air temperature for storage-40...185 °F (-40...85 °C)
Ambient air temperature for operation-13...158 °F (-25...70 °C)
MPN