Skip to main content
Schneider Electric LV848121

Schneider Electric LV848121

MPNLV848121
Active

Circuit breaker frame, MasterPact MTZ3 63H1 fixed for MicroLogic X, 6300A, 100kA/415VAC (Icu), 4P

$40,474.48 – $42,498.20Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LV848121 key specifications
ParameterValue
Control typePush-button
Performance typeH1 100 kA 415 V AC
Product or component typeCircuit breaker
Voltage1000 V AC 50/60 Hz
[Ue] rated operational voltage690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage12 kV
[Icw] rated short-time withstand current100 kA 0.5 s 100 kA 1 s 100 kA 3 s
Line rated current6300 A 104 °F (40 °C)
[Ics] rated service breaking capacity100 kA 220/415 V AC 50/60 Hz 100 kA 440 V AC 50/60 Hz 100 kA 500/525 V AC 50/60 Hz 100 kA 660/690 V AC 50/60 Hz
[Icm] rated short-circuit making capacity220 kA 220/415 V AC 50/60 Hz 220 kA 440 V AC 50/60 Hz 220 kA 500/525 V AC 50/60 Hz 220 kA 660/690 V AC 50/60 Hz
[Icu] rated ultimate short-circuit breaking capacity100 kA 220/415 V AC 50/60 Hz 100 kA 440 V AC 50/60 Hz 100 kA 500/525 V AC 50/60 Hz 100 kA 660/690 V AC 50/60 Hz
Power dissipation in650 W

All specifications

LV848121 additional specifications
ParameterValue
Poles description4P
IP degree of protectionIP30 conforming to EN 60529
Mounting modeFixed
Mounting supportRails Base plate
Connection pitch9.06 in (230 mm)
Upside connectionRear
Downside connectionRear
Maximum closing response time80 ms
Pollution degree3 IEC 60947-1
Operating altitude0...6561.68 ft (0...2000 m) without derating 2000...5000 m with derating
Depth11.8 in (300 mm)
Width39.3 in (997 mm)
Height13.9 in (352 mm)
Electrical durabilityAC-3 6000 cycles 440/690 V AC 50/60 Hz EN/IEC 60947-3 1500 cycles 440 V AC 50/60 Hz EN/IEC 60947-2 1500 cycles 690 V AC 50/60 Hz EN/IEC 60947-2 AC-23A 1500 cycles 440 V AC 50/60 Hz EN/IEC 60947-3 AC-23A 1500 cycles 690 V AC 50/60 Hz EN/IEC 60947-3
Mechanical durability10000 cycles with periodic preventive maintenance
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H IEC 61557-12
RangeMasterPacT
Control unitWithout control unit
Sensor rating3200 A 4000 A 5000 A 6300 A
Neutral positionLeft
Device short nameMTZ3 63 H1
Device applicationPower distribution protection
Selectivity categoryCategory B
Maximum breaking time25 ms
Suitability for isolationYes EN/IEC 60947-2
Ambient air temperature for storage-40...185 °F (-40...85 °C)
Ambient air temperature for operation-13...158 °F (-25...70 °C)
MPN
LV848121