Skip to main content
Schneider Electric LV848313

Schneider Electric LV848313

MPNLV848313
Active

Circuit breaker Masterpact MTZ2 32H2 - 3200 A - 3P drawout - w/o Micrologic

$14,082.99 – $14,787.12Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LV848313 key specifications
ParameterValue
Control typePush-button
Performance typeH2 100 kA 415 V AC
Product or component typeCircuit breaker
Voltage1000 V AC 50/60 Hz
[Ue] rated operational voltage690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage12 kV
[Icw] rated short-time withstand current85 kA 0.5 s 85 kA 1 s 75 kA 3 s
Line rated current3200 A 104 °F (40 °C)
[Ics] rated service breaking capacity100 kA 220/415 V AC 50/60 Hz 100 kA 440 V AC 50/60 Hz 85 kA 500/525 V AC 50/60 Hz 85 kA 660/690 V AC 50/60 Hz
[Icm] rated short-circuit making capacity220 kA 220/415 V AC 50/60 Hz 220 kA 440 V AC 50/60 Hz 187 kA 500/525 V AC 50/60 Hz 187 kA 660/690 V AC 50/60 Hz
[Icu] rated ultimate short-circuit breaking capacity100 kA 220/415 V AC 50/60 Hz 100 kA 440 V AC 50/60 Hz 85 kA 500/525 V AC 50/60 Hz 85 kA 660/690 V AC 50/60 Hz
Power dissipation in670 W

All specifications

LV848313 additional specifications
ParameterValue
Poles description3P
IP degree of protectionIP30 conforming to EN 60529
Mounting modeDrawout
Mounting supportRails Base plate
Connection pitch4.5 in (115 mm)
Upside connectionFront Rear
Downside connectionFront Rear
Maximum closing response time70 ms
Pollution degree3 IEC 60947-1
Operating altitude0...6561.68 ft (0...2000 m) without derating 2000...5000 m with derating
DepthDrawout circuit breaker with chassis: 15.9 in (403 mm) Drawout circuit breaker without chassis: 11.8 in (300 mm)
WidthDrawout circuit breaker with chassis: 17.4 in (441 mm) Drawout circuit breaker without chassis: 14.9 in (378 mm)
HeightDrawout circuit breaker with chassis: 17.3 in (439 mm) Drawout circuit breaker without chassis: 11.8 in (300 mm)
Electrical durabilityAC-3 6000 cycles 440/690 V AC 50/60 Hz EN/IEC 60947-3 2500 cycles 690 V AC 50/60 Hz EN/IEC 60947-2 5000 cycles 440 V AC 50/60 Hz EN/IEC 60947-2 AC-23A 2500 cycles 690 V AC 50/60 Hz EN/IEC 60947-3 AC-23A 5000 cycles 440 V AC 50/60 Hz EN/IEC 60947-3
Mechanical durability20000 cycles with periodic preventive maintenance
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H IEC 61557-12
RangeMasterPacT
Control unitWithout control unit
Sensor rating1600 A 2000 A 2500 A 3200 A
Device short nameMTZ2 32 H2
Device applicationPower distribution protection
Selectivity categoryCategory B
Maximum breaking time25 ms
Suitability for isolationYes EN/IEC 60947-2
Ambient air temperature for storage-40...185 °F (-40...85 °C)
Ambient air temperature for operation-13...158 °F (-25...70 °C)
Integrated instantaneous protection (DIN in kA peak)171...209 kA
MPN