Schneider Electric LV947285

MPNLV947285
Active

MicroLogic Active 5.0A control unit, no wireless, MasterPacT MTZ1/MTZ2/MTZ3, fixed circuit breakers, LSI protections

$1,684.41 – $1,768.63Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LV947285 key specifications
ParameterValue
Control typeWired control
Display typeLCD display - 320 x 240 pixels
Network typeAC
Metering typeCurrent I1, I2, I3, Iavg RMS Neutral current IN RMS Ground fault current Ig RMS Demand current I1, I2, I3, In, Iavg Frequency Phase sequence total Unbalance current
Protection typeOverload protection (long time) conforming to ANSI 49 Instantaneous short-circuit protection conforming to ANSI 50 Short time short-circuit protection conforming to ANSI 51
Type of measurementAmmeter
Product or component typeControl unit
Long time delay adjustment typeAdjustable in step of 0.5 s
Short-time delay adjustment typeAdjustable
Network and machine diagnosis typeSystem (HMI) health state overview: circuit breaker health state Contacts state: circuit breaker health state MicroLogic service life: circuit breaker health state Tripping cause indication: circuit breaker tripping cause Identification card: diagnostic data Configured alarms synthesis: diagnostic data Monitored function: diagnostic data Operation: diagnostic data MicroLogic test: test Protection test: test Selectivity test: test Trip context information: crisis management Operation: advanced diagnostic Breaker service life: circuit breaker health state
Instantaneous pick-up adjustment type iiAdjustable
[Ue] rated operational voltage690 V AC, +/- 10 %

All specifications

LV947285 additional specifications
ParameterValue
Network frequency50/60 Hz
Frequency measurement range40...70 Hz
Poles4P 3P
Protected poles description3P 3d 4P 3d 4P 3d + N/2 4P 4d 4P 3d + OSN
Communication port protocolNFC peer to peer 28800 bauds conforming to ISO 15963 USB peer to peer 115 kbauds
Mounting modeFixed
Mounting locationIndoor use only
Pollution degree3 conforming to IEC 60947-1
Relative humidity95 % at 55 °C conforming to IEC 60068-2-30
Operating altitude<= 5000 m with operational voltage derating 560 V AC
StandardsEN/IEC 60947-2 EN/IEC 60092-202 EN/IEC 60947-1 EN/IEC 60255-1 EN/IEC 61010-1
RangeMasterPacT
Data recordingData logs Event logs Alarm logs Time stamping Maintenance logs Min/max of instantaneous values
Thermal memoryYes
Trip unit rating250 A 400 A 630 A 800 A 1000 A 1250 A 1600 A 2000 A 2500 A 3200 A 4000 A 5000 A 6300 A
Device short nameMicroLogic Active 5.0 A
Device applicationEquipment protection, monitoring and control
Measurement accuracyCurrent I1, I2, I3, Iavg, Idemand for MTZ1: +/- 1.5 % 40...1600 x 1.2 A Current I1, I2, I3, Iavg, Idemand for MTZ2: +/- 1.5 % 40...4000 x 1.2 A Current I1, I2, I3, Iavg, Idemand for MTZ3: +/- 1.5 % 80...6300 x 1.2 A Neutral current IN: +/- 1.5 % Ground fault current Ig: +/- 10 % Frequency: +/- 0.005 Hz Unbalance current: +/- 0.5 %
Measurement categoryCategory IV conforming to IEC 61010-2-30
Overvoltage categoryIV conforming to IEC 61010-1
Trip unit technologyElectronic
Neutral protection setting1 x Ir (4P 4d) 0.5 x Ir (4P 3d + N/2) 1.6 x Ir (4P 3d + OSN) No protection (4P 3d)
Circuit breaker applicationDistribution IEC standard
Environmental characteristicWet location not approved for use conforming to IEC 61010-1
Electromagnetic compatibilityElectrostatic discharge immunity test conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test conforming to IEC 61000-4-4 1.2/50 µs shock waves immunity test conforming to IEC 61000-4-5 Conducted RF disturbances conforming to IEC 61000-4-6 Conducted and radiated emissions A conforming to CISPR 22
Trip unit protection functionsLSI
Zone selective interlocking ZSIWith
Ambient air temperature for operation-25...70 °C (operating) -35 °C (for start-up of product)
[Tr] Long-Time delay adjustment range0.5...30 s at 6 x Ir
[Ir] long time pick-up adjustment range0.4...1 x In adjustable in step of 1 A
[Tsd] Short-Time delay adjustment range0.1...0.8 s I²t=on 0...0.8 s I²t=off
[Isd] short-time pick-up adjustment range1.5...10 x Ir adjustable in step of 0.1 x Ir
[Ii] instantaneous pick-up adjustment range2...15 x In adjustable in step of 0.1 x In Ii enable on/off
[Li mode] instantaneous delay adjustment range20 ms in standard
MPN
LV947285