Schneider Electric LV947285
MPNLV947285
Active
MicroLogic Active 5.0A control unit, no wireless, MasterPacT MTZ1/MTZ2/MTZ3, fixed circuit breakers, LSI protections
$1,684.41 – $1,768.63Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Control type | Wired control |
| Display type | LCD display - 320 x 240 pixels |
| Network type | AC |
| Metering type | Current I1, I2, I3, Iavg RMS Neutral current IN RMS Ground fault current Ig RMS Demand current I1, I2, I3, In, Iavg Frequency Phase sequence total Unbalance current |
| Protection type | Overload protection (long time) conforming to ANSI 49 Instantaneous short-circuit protection conforming to ANSI 50 Short time short-circuit protection conforming to ANSI 51 |
| Type of measurement | Ammeter |
| Product or component type | Control unit |
| Long time delay adjustment type | Adjustable in step of 0.5 s |
| Short-time delay adjustment type | Adjustable |
| Network and machine diagnosis type | System (HMI) health state overview: circuit breaker health state Contacts state: circuit breaker health state MicroLogic service life: circuit breaker health state Tripping cause indication: circuit breaker tripping cause Identification card: diagnostic data Configured alarms synthesis: diagnostic data Monitored function: diagnostic data Operation: diagnostic data MicroLogic test: test Protection test: test Selectivity test: test Trip context information: crisis management Operation: advanced diagnostic Breaker service life: circuit breaker health state |
| Instantaneous pick-up adjustment type ii | Adjustable |
| [Ue] rated operational voltage | 690 V AC, +/- 10 % |
All specifications
| Parameter | Value |
|---|---|
| Network frequency | 50/60 Hz |
| Frequency measurement range | 40...70 Hz |
| Poles | 4P 3P |
| Protected poles description | 3P 3d 4P 3d 4P 3d + N/2 4P 4d 4P 3d + OSN |
| Communication port protocol | NFC peer to peer 28800 bauds conforming to ISO 15963 USB peer to peer 115 kbauds |
| Mounting mode | Fixed |
| Mounting location | Indoor use only |
| Pollution degree | 3 conforming to IEC 60947-1 |
| Relative humidity | 95 % at 55 °C conforming to IEC 60068-2-30 |
| Operating altitude | <= 5000 m with operational voltage derating 560 V AC |
| Standards | EN/IEC 60947-2 EN/IEC 60092-202 EN/IEC 60947-1 EN/IEC 60255-1 EN/IEC 61010-1 |
| Range | MasterPacT |
| Data recording | Data logs Event logs Alarm logs Time stamping Maintenance logs Min/max of instantaneous values |
| Thermal memory | Yes |
| Trip unit rating | 250 A 400 A 630 A 800 A 1000 A 1250 A 1600 A 2000 A 2500 A 3200 A 4000 A 5000 A 6300 A |
| Device short name | MicroLogic Active 5.0 A |
| Device application | Equipment protection, monitoring and control |
| Measurement accuracy | Current I1, I2, I3, Iavg, Idemand for MTZ1: +/- 1.5 % 40...1600 x 1.2 A Current I1, I2, I3, Iavg, Idemand for MTZ2: +/- 1.5 % 40...4000 x 1.2 A Current I1, I2, I3, Iavg, Idemand for MTZ3: +/- 1.5 % 80...6300 x 1.2 A Neutral current IN: +/- 1.5 % Ground fault current Ig: +/- 10 % Frequency: +/- 0.005 Hz Unbalance current: +/- 0.5 % |
| Measurement category | Category IV conforming to IEC 61010-2-30 |
| Overvoltage category | IV conforming to IEC 61010-1 |
| Trip unit technology | Electronic |
| Neutral protection setting | 1 x Ir (4P 4d) 0.5 x Ir (4P 3d + N/2) 1.6 x Ir (4P 3d + OSN) No protection (4P 3d) |
| Circuit breaker application | Distribution IEC standard |
| Environmental characteristic | Wet location not approved for use conforming to IEC 61010-1 |
| Electromagnetic compatibility | Electrostatic discharge immunity test conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test conforming to IEC 61000-4-4 1.2/50 µs shock waves immunity test conforming to IEC 61000-4-5 Conducted RF disturbances conforming to IEC 61000-4-6 Conducted and radiated emissions A conforming to CISPR 22 |
| Trip unit protection functions | LSI |
| Zone selective interlocking ZSI | With |
| Ambient air temperature for operation | -25...70 °C (operating) -35 °C (for start-up of product) |
| [Tr] Long-Time delay adjustment range | 0.5...30 s at 6 x Ir |
| [Ir] long time pick-up adjustment range | 0.4...1 x In adjustable in step of 1 A |
| [Tsd] Short-Time delay adjustment range | 0.1...0.8 s I²t=on 0...0.8 s I²t=off |
| [Isd] short-time pick-up adjustment range | 1.5...10 x Ir adjustable in step of 0.1 x Ir |
| [Ii] instantaneous pick-up adjustment range | 2...15 x In adjustable in step of 0.1 x In Ii enable on/off |
| [Li mode] instantaneous delay adjustment range | 20 ms in standard |
MPN