Skip to main content
Schneider Electric LX1FH1102

Schneider LX1FH1102 Contactor Coil, 110-115V AC, Obsolete

MPNLX1FH1102
Obsolete

Schneider Electric TeSys F contactor coil, LX1FH1102, 110...115 V AC 40-400 Hz, 650 VA inrush, 10 VA holding.

$57.15 – $170.59Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LX1FH1102 specifications
ParameterValue
Control circuit typeAC 40...400 Hz
Product or component typeContactor coil
Coil voltage110...115 V AC 40...400 Hz
Control circuit voltage limitsDrop-out 0.35...0.55 Uc 40...400 Hz 131 °F (55 °C)) Operational 0.85...1.1 Uc 40...400 Hz 131 °F (55 °C))
Inrush power in650 VA 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))
Hold-in power consumption in10 VA 40...400 Hz cos phi 0.3 (at 68 °F (20 °C))
Mechanical durability10 Mcycles
RangeTeSys
CategoryUS10I1222341
Operating time100...170 ms opening 40...65 ms closing
Coil technologyWithout built-in suppressor module
Heat dissipation8 W 40...400 Hz
Device short nameLX1FH
Average resistance18.7 Ohm inrush 68 °F (20 °C) 440 Ohm holding 68 °F (20 °C)
Maximum operating rate2400 cyc/h 131 °F (55 °C)
Ambient air temperature for operation23...131 °F (-5...55 °C)

Product details

Coil Electrical Details

The coil dissipates 8 W at 40-400 Hz. Inrush circuit: 18.7 Ω at 20 °C; holding circuit: 440 Ω. Drop-out threshold is 0.35-0.55 Uc; pick-up is 0.85-1.1 Uc. Ambient range -5 to 55 °C.

Frequently asked questions

What is the rated coil voltage for LX1FH1102?

110-115 V AC at 40-400 Hz.

What are the inrush and holding power values?

Inrush 650 VA, holding 10 VA, both at 20 °C.

MPN
LX1FH1102