Coil Electrical Details
The coil dissipates 8 W at 40-400 Hz. Inrush circuit: 18.7 Ω at 20 °C; holding circuit: 440 Ω. Drop-out threshold is 0.35-0.55 Uc; pick-up is 0.85-1.1 Uc. Ambient range -5 to 55 °C.
Schneider Electric TeSys F contactor coil, LX1FH1102, 110...115 V AC 40-400 Hz, 650 VA inrush, 10 VA holding.
| Parameter | Value |
|---|---|
| Control circuit type | AC 40...400 Hz |
| Product or component type | Contactor coil |
| Coil voltage | 110...115 V AC 40...400 Hz |
| Control circuit voltage limits | Drop-out 0.35...0.55 Uc 40...400 Hz 131 °F (55 °C)) Operational 0.85...1.1 Uc 40...400 Hz 131 °F (55 °C)) |
| Inrush power in | 650 VA 40...400 Hz cos phi 0.9 (at 68 °F (20 °C)) |
| Hold-in power consumption in | 10 VA 40...400 Hz cos phi 0.3 (at 68 °F (20 °C)) |
| Mechanical durability | 10 Mcycles |
| Range | TeSys |
| Category | US10I1222341 |
| Operating time | 100...170 ms opening 40...65 ms closing |
| Coil technology | Without built-in suppressor module |
| Heat dissipation | 8 W 40...400 Hz |
| Device short name | LX1FH |
| Average resistance | 18.7 Ohm inrush 68 °F (20 °C) 440 Ohm holding 68 °F (20 °C) |
| Maximum operating rate | 2400 cyc/h 131 °F (55 °C) |
| Ambient air temperature for operation | 23...131 °F (-5...55 °C) |
The coil dissipates 8 W at 40-400 Hz. Inrush circuit: 18.7 Ω at 20 °C; holding circuit: 440 Ω. Drop-out threshold is 0.35-0.55 Uc; pick-up is 0.85-1.1 Uc. Ambient range -5 to 55 °C.
110-115 V AC at 40-400 Hz.
Inrush 650 VA, holding 10 VA, both at 20 °C.