Coil Electrical Details
The coil dissipates 8 W at 40-400 Hz. Inrush circuit: 18.7 Ω at 20 °C; holding circuit: 440 Ω. Drop-out threshold is 0.35-0.55 Uc; pick-up is 0.85-1.1 Uc. Ambient range -5 to 55 °C.

Schneider Electric TeSys F contactor coil, LX1FH1102, 110...115 V AC 40-400 Hz, 650 VA inrush, 10 VA holding.
| Parameter | Value |
|---|---|
| Range | TeSys |
| Operating time | 100...170 ms opening 40...65 ms closing |
| Coil technology | Without built-in suppressor module |
| Heat dissipation | 8 W 40...400 Hz |
| Device short name | LX1FH |
| Average resistance | 18.7 Ohm inrush 68 °F (20 °C) 440 Ohm holding 68 °F (20 °C) |
| Inrush power in | 650 VA 40...400 Hz cos phi 0.9 (at 68 °F (20 °C)) |
| Control circuit type | AC 40...400 Hz |
| Mechanical durability | 10 Mcycles |
| Maximum operating rate | 2400 cyc/h 131 °F (55 °C) |
| Product or component type | Contactor coil |
| Coil voltage | 110...115 V AC 40...400 Hz |
| Control circuit voltage limits | Drop-out 0.35...0.55 Uc 40...400 Hz 131 °F (55 °C)) Operational 0.85...1.1 Uc 40...400 Hz 131 °F (55 °C)) |
| Hold-in power consumption in | 10 VA 40...400 Hz cos phi 0.3 (at 68 °F (20 °C)) |
| Ambient air temperature for operation | 23...131 °F (-5...55 °C) |
The coil dissipates 8 W at 40-400 Hz. Inrush circuit: 18.7 Ω at 20 °C; holding circuit: 440 Ω. Drop-out threshold is 0.35-0.55 Uc; pick-up is 0.85-1.1 Uc. Ambient range -5 to 55 °C.
110-115 V AC at 40-400 Hz.
Inrush 650 VA, holding 10 VA, both at 20 °C.
Alternative models and sibling configurations in the same Schneider Electric series. For obsolete or discontinued parts, these models can serve as compatible replacements or functional alternatives for plant maintenance.
No related articles