Specifications

LX1G3QKUEN key specifications
ParameterValue
Product or component typeContactor coil
Coil voltage100...250 V AC/DC 50/60 Hz
Control circuit voltage limitsOperational 0.8...1.1 Uc 140 °F (60 °C)) Drop-out 0...0.45 Uc 140 °F (60 °C))
Inrush power in485 VA 240 V AC, 50 Hz
Hold-in power consumption in9.4 VA 240 V AC, 50 Hz
Poles description3P
IP degree of protectionIP20 IEC 60529
Connections - terminalsControl circuit push-in termination 1 0.0003...0.004 in² (0.2...2.5 mm²) solid stranded without cable end sleeve AWG 26...AWG 12 Control circuit push-in termination 1 0.0004...0.004 in² (0.25...2.5 mm²) flexible with cable end sleeve AWG 24...AWG 14 Control circuit push-in termination 2 0.0008...0.002 in² (0.5...1.0 mm²) rigid or stranded with cable end sleeve AWG 20...AWG 18
Pollution degree3 IEC 60947-1
Operating altitude9842.52 ft (3000 m) without derating 5000 m with derating factor
Depth3.7 in (94.0 mm)
Width4.2 in (105.7 mm)

All specifications

LX1G3QKUEN additional specifications
ParameterValue
Height5.7 in (144.5 mm)
Mechanical durability5 Mcycles
StandardsEN/IEC 60947-4-1 UL 60947-4-1A CSA C22.2 No 60947-4-1
RangeTeSys
CategoryUS10I1222328
Operating time20...35 ms opening 40...55 ms closing
Coil technologyBuilt-in bidirectional peak limiting
Quantity per set1
Device short nameLX1G
Maximum operating rate600 cyc/mn 140 °F (60 °C)
Electromagnetic compatibilityEMC immunity conforming to IEC 60947-4-1 Emission tests criteria A conforming to IEC 60947-4-1 Immunity to radiated radio-electrical interference - test level: 20 V/m conforming to EN/IEC 61000-4-3 Voltage dips and interruptions immunity test conforming to SEMI F47
Ambient air temperature for storage-76...176 °F (-60...80 °C)
Ambient air temperature for operation-13...140 °F (-25...60 °C)
Permissible ambient air temperature around the device-40...158 °F (-40...70 °C) at Uc

Product details

Control coil module for TeSys D contactors

The Schneider LX1G3QKUEN is a TeSys-series contactor coil module rated for 100...250 V AC/DC control voltage, built for mounting onto TeSys D contactors. It carries built-in bidirectional peak limiting on the coil, so you can skip external suppression networks on most pilot-duty circuits.

Terminals and wiring

Control circuit wiring uses push-in terminals accepting 0.2…2.5 mm² solid or stranded (with or without ferrule), AWG 26…12. Two termination points per pole allow daisy-chaining. IP20 protected, pollution degree 3 rated for industrial environments.

Electrical characteristics

Inrush draws 365 W DC or 485 VA at 240 V 50 Hz; hold-in drops to 5.2 W DC or 9.4 VA. Opening time 20…35 ms, closing 40…55 ms. Coil limits: operational 0.8…1.1 Uc, drop-out below 0.45 Uc at 60 °C.

Environmental and standards

Rated for -25…60 °C operating, -60…80 °C storage, with derating above 3000 m altitude. Conforms to EN/IEC 60947-4-1, UL 60947-4-1A, CSA C22.2 No 60947-4-1. EMC immunity meets criteria A per the same standard. Production status is active; no end-of-life notice.

Frequently asked questions

What is the depth of the LX1G3QKUEN?

The depth is 3.7 in (94.0 mm) per the spec sheet.

What product range does the LX1G3QKUEN belong to?

It is part of the TeSys range from Schneider Electric.

What compliance standards does the LX1G3QKUEN meet?

It conforms to EN/IEC 60947-4-1, UL 60947-4-1A, and CSA C22.2 No 60947-4-1. It also meets EMC immunity criteria A per IEC 60947-4-1.