Schneider Electric LX9FK931

Square D LX9FK931 TeSys Coil, 220-230V AC/DC, Obsolete

MPNLX9FK931
Obsolete

Square D TeSys specific contactor coil, LX9FK931, 220–230 V AC/DC, obsolete.

$332.74 – $441.00Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

LX9FK931 specifications
ParameterValue
Control circuit typeAC 40...400 Hz low consumption DC low consumption
Product or component typeSpecific contactor coil
Coil voltage220...230 V AC 40...400 Hz 220...230 V DC
Control circuit voltage limitsOperational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.3...0.5 Uc 131 °F (55 °C))
Inrush power in550 VA 40...400 Hz (at 68 °F (20 °C))
Hold-in power consumption in31 VA 40...400 Hz (at 68 °F (20 °C))
Mechanical durability10 Mcycles
RangeTeSys
CategoryUS10I1222341
Operating time60 ms opening 50 ms closing
Coil technologyWithout built-in suppressor module
Heat dissipation15...18.3 W
Device short nameLX9FK
Average resistance89.9 Ohm inrush 68 °F (20 °C) 770 Ohm holding 68 °F (20 °C)
Maximum operating rate3600 cyc/h 158 °F (70 °C)
Inductance of closed circuit4 H
Ambient air temperature for operation23...131 °F (-5...55 °C)

Product details

Key ratings you care about

LX9FK931 coil: inrush 550 VA, holding 31 VA at 68 °F. Operational voltage limits: 0.85–1.1 Uc; drop-out: 0.3–0.5 Uc. No built-in suppressor module. That means you need an external flyback diode or RC snubber across the coil if you're switching it with a PLC or relay. Skip it and the back-EMF can weld your contacts or fry the output card. The coil's average resistance is 89.9 Ω inrush, 770 Ω holding at 68 °F (20 °C) — these numbers help size the external suppression, especially for DC operation where the holding current is much lower than inrush. Heat dissipation runs 15...18.3 W continuous. That's warm, not hot, but if you're stacking coils in a closed panel, add a little ventilation clearance. That's solid for frequent cycling like conveyor or pump control. Opening time is 60 ms, closing time 50 ms. That's typical for a large TeSys coil — not lightning fast, but consistent for interlocking sequences.

Frequently asked questions

What are the key electrical ratings of the LX9FK931?

Control voltage is 220...230 V AC (40–400 Hz) or 220...230 V DC. Inrush power 550 VA, holding power 31 VA. Coil resistance: inrush 89.9 Ω, holding 770 Ω at 20 °C. Heat dissipation 15...18.3 W. Opening time 60 ms, closing 50 ms.

How do I source an obsolete LX9FK931?

Through independent surplus or broker channels. We can quote to order from available stock; each coil is functionally verified before shipping. No factory lead time available.

Does the LX9FK931 have a built-in suppression module?

No, it has no built-in suppressor module. You must add external suppression (like a flyback diode for DC or an RC snubber for AC) when switching the coil with electronic outputs.