Schneider Electric M9D11640
MPNM9D11640
Obsolete
Residual current breaker with overcur. prot. (RCBO), Multi9 N40 Vigi, 1P+N, 40A, C curve, 6000A/6kA, AC type, 30mA
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Control type | Toggle |
| Network type | AC |
| Product or component type | Residual current breaker with overcurrent protection (RCBO) |
| Voltage | 400 V AC 50 Hz EN/IEC 60947-2 |
| [Ue] rated operational voltage | 240 V AC 50 Hz |
| [Uimp] rated impulse withstand voltage | 4 kVEN/IEC 60947-2 |
| Surge current | 250 A |
| Breaking capacity | 6 kA Icu 240 V AC 50 Hz EN/IEC 60947-2 6000 A Icn 240 V AC 50 Hz EN/IEC 61009-1 |
| Line rated current | 40 A 122 °F (50 °C) EN/IEC 60947-2 |
| Residual current tripping technology | Voltage independent |
| [Ics] rated service breaking capacity | 4.5 kA 75 % EN/IEC 60947-2 - 240 V AC 50 Hz |
| Network frequency | 50 Hz |
All specifications
| Parameter | Value |
|---|---|
| Poles description | 1P + N |
| Number of protected poles | 1 |
| Utilisation category | Category A EN/IEC 60947-2 |
| IP degree of protection | IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529 |
| Mounting mode | Clip-on |
| Mounting support | DIN rail |
| Connection pitch | 0.4 in (9 mm) between phase and neutral |
| Wire stripping length | 0.5 in (13 mm) for top or bottom connection |
| Connections - terminals | Tunnel type terminal top or bottom) 0.001...0.02 in² (0.75...16 mm²) - rigid Tunnel type terminal top or bottom) 0.0005...0.02 in² (0.33...10 mm²) - flexible Tunnel type terminal top or bottom) 0.0005...0.02 in² (0.33...10 mm²) - flexible with ferrule |
| Pollution degree | 3 EN/IEC 60947-2 |
| Relative humidity | 95 % 131 °F (55 °C) |
| Color | Gray |
| Depth | 2.8 in (70 mm) |
| Width | 1.4 in (36 mm) |
| Height | 3.2 in (81 mm) |
| Electrical durability | 10000 cycles |
| Mechanical durability | 20000 cycles |
| Standards | EN/IEC 61009-1 EN/IEC 60947-2 |
| Range | Multi9 |
| Category | US10DE200908 |
| Curve code | C |
| 9 mm pitches | 4 |
| Tropicalisation | 2 IEC 60068-1 |
| Limitation class | 3 EN/IEC 61009-1 |
| Local signalling | ON/OFF indication Fault indication |
| Neutral position | Left |
| Device short name | N40 Vigi |
| Tightening torque | 17.7 lbf.in (2 N.m) top or bottom |
| Device application | Distribution |
| Overvoltage category | IV |
| Trip unit technology | Thermal-magnetic |
| Magnetic tripping limit | 8.5 x In +/- 20 % AC |
| Earth-leakage protection | Integrated |
| Provision for padlocking | Padlockable |
| Earth-leakage sensitivity | 30 mA |
| Suitability for isolation | Yes EN/IEC 60947-2 |
| Contact position indicator | Yes |
| Electromagnetic compatibility | 8/20 µs impulse withstand, 250 A |
| Earth-leakage protection class | Type AC |
| Rated breaking and making capacity | Idm 3000 A 240 V AC 50 Hz EN/IEC 61009-1 |
| Ambient air temperature for storage | -22...158 °F (-30...70 °C) |
| Earth-leakage protection time delay | Instantaneous |
| Ambient air temperature for operation | 23...140 °F (-5...60 °C) |
MPN