Skip to main content
Schneider Electric METSECT5CC025

METSECT5CC025 PowerLogic 250/5 Current Transformer, Obsolete

MPNMETSECT5CC025
Obsolete

Schneider Electric PowerLogic METSECT5CC025, 250/5 A solid-core current transformer, Class 0.5/1/3, IP20, obsolete.

$20.32Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

METSECT5CC025 key specifications
ParameterValue
Current transformer typeTropicalised for cable Solid core
Product or component typeCurrent transformer
Dynamic withstand current2.5 Ith
Voltage3 kV 50 Hz for 1 minute
[Ue] rated operational voltage< 720 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage3 kV
Secondary current5 A
Current250 A
Current transformer ratio250/5
[Ith] conventional free air thermal current15 kA
IP degree of protectionIP20
Mounting modeBy screws Clip-on

All specifications

METSECT5CC025 additional specifications
ParameterValue
Mounting supportMounting plate DIN rail
Cable outer diameter21 mm
Relative humidity0...95 %
DepthFrame : 30 mm Total : 37 mm
WidthOutside: 44 mm
HeightOutside: 65 mm
StandardsVDE 0414 IEC 61869-2
RangePowerLogic
SealingWith
Diameter21 mm
AccuracyClass 0.5 at 5 VA Class 1 at 6 VA Class 3 at 7 VA
Maximum safety factor5
Electrical insulation classClass B
Ambient air temperature for operation-25...60 °C

Product details

The METSECT5CC025 is a 250/5 A solid-core current transformer from the PowerLogic range, tropicalised for cable mounting. It serves metering and protection circuits where a fixed ratio and through-hole diameter of 21 mm are sufficient—common in panel feeder monitoring and distribution board retrofits. The accuracy class rides on the burden: Class 0.5 at 5 VA for revenue-grade metering, Class 1 at 6 VA for general instrumentation, Class 3 at 7 VA for protection relays. Rated insulation voltage 3 kV for 1 minute, impulse withstand 3 kV, conventional thermal current 15 kA, dynamic withstand 2.5 Ith.

This CT is obsolete. It complies with VDE 0414 and IEC 61869-2.

Mounts by screw or clip-on on a mounting plate or DIN rail. Outside dimensions 44 x 65 mm, frame depth 30 mm, total depth 37 mm. Cable diameter limit 21 mm. Sealing included. IP20—dry indoor panel only. Operating temperature -25 to 60 °C, humidity 0–95 %. Electrical insulation Class B. No auxiliary supply needed; secondary is 5 A at 50/60 Hz, up to 720 V AC. Keep the secondary shorted when not connected to a burden to avoid dangerous voltages.

For a BOM line where a 250/5 A, 21 mm window CT fits, this part works. Obsolete status means you source through RFQ—not a standard distributor shelf item. Quote against your required quantity and delivery window.

Frequently asked questions

What compliance documents come with this CT?

The part complies with VDE 0414 and IEC 61869-2. No RoHS, REACH, or UL documentation is specified in the available records—verify with the supplier if certificates are required.

MPN
METSECT5CC025